Reverting old firmware

Migrate D20MX application definitions to SGConfig

Prerequisites
Procedure
D20MX HARDWARE USER'S MANUAL
A previously committed version of the firmware may be recovered from secondary
storage.
This feature is intended to be used when the primary version of the firmware has become
corrupt. Reverting the firmware copies the firmware from secondary storage into the
primary storage.
If, after downloading a new version of the firmware, an issue is identified in the new
firmware, the previous version may be recovered. This is only possible if the new firmware
has not been committed; see Section: Committing new firmware.
To commit new firmware:
1.
Login as a user that has Maintenance or Read/Write access privileges.
2.
Enter the D20M Shell.
3.
Enter the revert command
Result: A prompt appears to confirm copying the firmware from Secondary to Primary.
4.
Enter yes to confirm the copy operation. If anything else is entered, the command is
canceled.
Result: The firmware copy operation begins. Both 'vxworks' and 'appl.out' are copied.
This operation takes approximately 3 minutes.
DO NOT shut off the power to the D20MX while the copy operation is in progress. If power
to the D20MX is disrupted, during the copy operation, the firmware will likely be corrupted.
5.
Once the copy operation has completed, enter the boot command to restart the
D20MX with the reverted firmware.
Use this information to migrate the D20MX application definitions to SGConfig. This step
only needs to be performed once on a configuration computer.
Before you can migrate the D20MX application definitions to SGConfig, the following
components must be present:
SGConfig 7.2 or higher installed on the configuration computer.
The D20MX Documentation CD (part number 588-0075 V120) installed in a CD/DVD
drive of the configuration computer.
To migrate the D20MX application definitions to SGConfig:
Ignore any steps that refer to dialogs where you selected "Do not show this message
again".
1.
Start SGConfig.
Result: The Welcome to SGConfig screen appears.
2.
Click the GE button > Migration Wizard.
Result: The Welcome to the Migration Wizard screen appears.
3.
Click Next.
Result: The Select Task screen appears.
4.
Select Import application definitions and click Next.
Result: The Import application definitions screen appears.