Wiring; Terminal Connection Diagram - Mitsubishi FR-F500 Instruction Manual

Transistorized inverter
Hide thumbs Also See for FR-F500:
Table of Contents

Advertisement

2.2 Wiring

2.2 Wiring

2.2.1 Terminal connection diagram

EC version
NFB
3-phase AC
power supply
Jumper
NFB
3-phase AC
power supply
24VDC power output and external transistor common
(Contact input common for source logic)
Forward rotation start
Reverse rotation start
Start self-holding selection
Multi-speed selection
Second acceleration/deceleration
time selection
Current input selection
Selection of automatic restart
after instantaneous power failure
(Contact input common for sink logic)
Control input signals (no voltage input allowed)
Frequency setting signals (analog)
Frequency
3
2
setting
potentiometer
1
1/2W1k
Auxiliary input
L
1
L
2
L
3
L
11
L
21
R
S
T
R1
Jumper
S1
PC
STF
STR
STOP
RH
High
RM
Middle
RL
Low
JOG
Jog mode
RT
MRS
Output stop
RES
Reset
AU
CS
SD
10E( 10V)
10( 5V)
0 to 5VDC
2
0 to 10VDC
5
(Analog common)
Common
0 to
1
0 to 10VDC
Current input
4 (4 to 20mADC)
INSTALLATION AND WIRING
U
V
PU
W
connector
(RS-485)
P1
P
(Note)
PX
(Note)
PR
N
A
B
C
RUN
Running
SU
Up to frequency
IPF
Instantaneous power failure
OL
Overload
FU
Frequency detection
Open collector output common
SE
Common to sink and source
FM
Calibration
resistor*
Selected
SD
AM
5
5VDC
Selected
* Not needed when the operation panel (FR-DU04) or parameter unit
(FR-PU04) is used for calibration.
Used when calibration must be made near the frequency meter for
such a reason as a remote frequency meter. However, the
frequency meter needle may not deflect to full-scale if the
calibration resistor is connected.
In this case, use this resistor and the operation panel or
parameter unit together to make calibration.
9
EC version
P1
+
PX
PR
Motor
IM
Ground
Jumper
Remove this jumper when using FR-BEL.
Jumper
Note:Please do not alter or adjust terminals PR
and PX or the connecting jumper.
Alarm output
Open collector
outputs
Meter
(e.g. frequency meter)
Moving-coil type
1mA full-scale
( )
Analog signal output
(0 to 10VDC)
( )
Ground
Main circuit terminal
Control circuit input terminal
Control circuit output terminal

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents