5) Waiting time
Specify the waiting time between the receipt of data at the inverter from the computer and the transmission
of reply data. Set the waiting time in accordance with the response time of the computer between 0 and
150ms in 10ms increments (e.g. 1 = 10ms, 2 = 20ms).
Computer
Inverter
Inverter
Computer
Note: If the Pr. 123 "waiting time setting" value is not 9999, create the communication request data with no
"waiting time" in the data format. (The number of characters is decremented by 1.)
6) Response time
[Data sending time calculation expression]
1
Number of data characters
Communication speed
(bps)
Communication specification
Name
Number of Bits
1 bit
Stop bit length
2 bits
7 bits
Data length
8 bits
Yes
1 bit
Parity check
No
0 bits
In addition to the bits in the above table, 1 bit is required for the start bit.
Minimum total number of bits ... 9 bits
Maximum total number of bits ... 12 bits
Data sending time
(refer to the following calculation expression)
Inverter data processing time = waiting time + data check time
Computer
Inverter
STX
Inverter
10ms or
more required
Computer
Data sending time
(refer to the following calculation expression)
Data sending time
(refer to the following calculation expression)
Inverter data processing time = waiting time + data check time
Computer
Inverter
Inverter
10ms or
more required
Computer
Data sending time
(refer to the following calculation expression)
Communication specification
(Refer to page 111)
Inverter data processing time
= waiting time
(set value 10ms)
(set value 10ms)
(12ms)
ACK
ENQ
10ms or
more required
(set value 10ms)
(12ms)
ENQ
(Total number of bits)
= Data sending time (s)
(See below)
113
PARAMETERS
+ data check time
(12ms)
4