Leakage Currents And Countermeasures - Mitsubishi FR-F500 Instruction Manual

Transistorized inverter
Hide thumbs Also See for FR-F500:
Table of Contents

Advertisement

# # # # Example of counter measures against noise
Install filter (FR-BLF,FR-
BSF01) to inverter input side.
Inverter power
supply
Separate inverter and power line
30cm (11.81inches) or more
(at least 10cm (3.94inches))
from sensor circuit.
Control power
supply
Do not ground control box directly.
Stop earthing the control cable.

2.3.4 Leakage currents and countermeasures

Due to the static capacitance existing in the inverter I/O wiring and motor, leakage currents flow through
them. Since their values depend on the static capacitance, carrier frequency, etc. take counter measures
using the following methods.
( 1 ) To-ground leakage currents
Leakage currents may flow not only into the inverter's own line but also into the other line through the ground
cable, etc. These leakage currents may operate earth leakage circuit breakers and earth leakage relays
unnecessarily.
# # # # Countermeasures
Decrease the carrier frequency (Pr. 72) of the inverter.
Note that motor noise increases. Selection of Soft-PWM (Pr. 240) will make it unoffending.
By using earth leakage circuit breakers designed for harmonics and surge suppression (e.g. Mitsubishi's
Progressive Super Series) in the inverter's own line and other line, operation can be performed with the
carrier frequency kept high (with low noise).
# # # # To-ground leakage current
Note that a long wiring length will increase leakage currents. Decrease the carrier frequency of the
inverter to reduce leakage currents.
Higher motor capacity leads to larger leakage currents. Larger leakage currents occur in 400V class than
in 200V class.
Control box
FR-
BLF
Install filter FR-BIF to
inverter input side.
INSTALLATION AND WIRING
Reduce carrier
frequency.
FR-
Inverter
BLF
FR-
BIF
Use twisted pair
shielded cable.
Power
supply for
sensor
Do not ground shield but connect
it to signal common cable.
35
Install filter (FR-BLF,FR-BSF01)
to inverter output side.
Motor
Use 4-core cable for motor
power cable and use one
cable as ground cable.
Sensor