Toshiba R410A Service Manual page 77

Super heat recovery multi system
Hide thumbs Also See for R410A:
Table of Contents

Advertisement

7-1-4. Applied Control in Indoor Unit
n Remote location ON/OFF control box (TCB-IFCB-4E)
[Wiring and setup]
• Use the exclusive connector for connection with the indoor control P .C. board.
• In a group control, the system can operate when connecting with any indoor unit (Control P .C. board) in the
group. However when taking out the operation/error signal from the other unit, it is necessary to take out from
each unit individually.
(1) Control items
1) Start/Stop input signal : Operation start/stop in unit
2) Operation signal
3) Error signal
(2) Wiring diagram using remote control interface (TCB-IFCB-4E)
Input
IFCB-4E : No voltage ON/OFF serial signal
Output
No voltage contact for operation, error display
Contact capacity: Below Max. AC240V 0.5A
Indoor control P.C. board
Remote controller prohibition/clear input
Operation signal output
Error signal output
: Output during normal operation
: Output during alarm
(Serial communication error or indoor/outdoor protective device) operation
Start/Stop input
1
COM (GND)
2
3
4
COM (+12V)
5
6
CN61
T10
(YEL)
Remote location ON/OFF control box
(TCB-IFCB-4E)
1
2
3
4
CN06
1
2
3
4
5
6
CN13
~
Power supply 220–240V,
77
ON/OFF serial
signal input
COM
Operation signal output
Error signal output
50Hz

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents