Toshiba R410A Service Manual page 126

Super heat recovery multi system
Hide thumbs Also See for R410A:
Table of Contents

Advertisement

Check code
Outdoor 7-segment display
Main
remote
controller Check code
Sub-code
E31
E31
01: IPDU1 error
02: IPDU2 error
03: IPDU1, 2 errors
04: Fan IPDU error
05: IPDU1 + Fan IPDU error
06: IPDU2 + Fan IPDU error
07: All IPDU error or communication error
between IPDU and I/F P .C. board or
outdoor I/F P .C. board error
F01
F02
F03
F04
F04
F05
F05
F06
F06
F07
F07
F08
F08
F10
F12
F12
01: TS1
02: TS2
Detected
Check code
AI-NET
position
name
central control
remote controller
CF
I/F
IPDU
communication
error
OF
Indoor unit Indoor TCJ
sensor error
Od
Indoor unit Indoor TC2
sensor error
93
Indoor unit Indoor TC1
sensor error
19
I/F
TD1 sensor
error
A1
I/F
TD2 sensor
error
18
I/F
TE1 sensor
error
18
I/F
TL sensor error
1b
I/F
TO sensor
error
OC
Indoor
Indoor TA
sensor error
A2
I/F
TS1, TS2
sensor error
Status
Error detection condition
All stop
Communication of each IPDU
(P .C. board) in inverter box
interrupted.
Corresponding
• Resistance value of sensor is
unit only stops
infinite or zero. (Open/Short)
Corresponding
• Resistance value of sensor is
unit only stops.
infinite or zero (Open/Short).
Corresponding
• Resistance value of sensor is
unit only stops.
infinite or zero (Open/Short).
All stop
• Resistance value of sensor is
infinite or zero (Open/Short)
All stop
• Resistance value of sensor is
infinite or zero (Open/Short)
All stop
• Resistance value of sensor is
infinite or zero (Open/Short).
All stop
• Resistance value of sensor is
infinite or zero (Open/Short).
All stop
• Resistance value of sensor is
infinite or zero (Open/Short).
Corresponding
• Resistance value of sensor is
unit only stops.
infinite or zero (Open/Short).
All stop
• Resistance value of sensor is
infinite or zero (Open/Short).
Check item (position)
• Check connection of communication connector and
disconnection between IPDU and I/F P .C. board.
• Check outdoor P .C. board (I/F , IPDU, Fan IPDU) error.
• Check external noise.
• Check power supply P .C. board for fan error.
• Check connection/cabling of TCJ sensor connector.
• Check characteristics of TCJ sensor resistance value.
• Check indoor P .C. board error.
• Check connection/cabling of TC2 sensor connector.
• Check characteristics of TC2 sensor resistance value.
• Check indoor P .C. board error.
• Check connection/cabling of TC1 sensor connector.
• Check characteristics of TC1 sensor resistance value.
• Check indoor P .C. board error.
• Check connection of TD1 sensor connector.
• Check characteristics of TD1 sensor resistance value.
• Check outdoor P .C. board (I/F) error.
• Check connection of TD2 sensor connector.
• Check characteristics of TD2 sensor resistance value.
• Check outdoor P .C. board (I/F) error.
• Check connection of TE1 sensor connector.
• Check characteristics of TE1 sensor resistance value.
• Check outdoor P .C. board (I/F) error.
• Check connection of TL sensor connector.
• Check characteristics of TL sensor resistance value.
• Check outdoor P .C. board (I/F) error.
• Check connection of TO sensor connector.
• Check characteristics of TO sensor resistance value.
• Check outdoor P .C. board (I/F) error.
• Check connection/cabling of TA sensor connector.
• Check characteristics of TA sensor resistance value.
• Check indoor P .C. board error.
• Check connection of TS1 or TS2 sensor connector.
• Check characteristics of TS1, TS2 sensor resistance value.
• Check outdoor P .C. board (I/F) error.

Hide quick links: