Toshiba R410A Service Manual page 69

Super heat recovery multi system
Hide thumbs Also See for R410A:
Table of Contents

Advertisement

Other cautions
1. Cooling operation in low ambient temperatures
1) The indoor unit freeze prevention control system (TC sensor) may decrease the command frequency to
the outdoor unit when low coil temperatures are detected.
2) The cooling capacity control may decrease the command frequency to the outdoor unit when low ambient
temperature is detected.
3) When the discharge temperature sensor value reaches 60°C or below, the frequency may be increased
above the required demand from the indoor unit.
2. PMV (Pulse Motor Valve) for outdoor unit
1) When the system power is turned on an audible "clicking" sound is omitted due to the PMV initialising,
this is a normal condition. When the outdoor unit is situated near other sources of noise, this sound may
not be noticeable.
2) Do not remove the driving part (head) of the PMV during operation as it may cause the PMV to malfunction.
3) When transporting or replacing the outdoor unit, never keep the driving part (head) removed from the
PMV body as the valve will be closed and may result in damage or failure due to sealed liquid compression.
4) When refitting the driving part (head) to the body of the PMV, apply pressure until a "click" sound can be
heard, complete the process by resetting the power to the system.
Release control list
Release item
High pressure release
Low pressure release
Discharge temp. release
Current release
Heat sink release
SV2 ON, SV41, SV42 ON
PMV3=45 pulses (All heating operation), 60 pulses (All cooling operation)
Operation frequency limit
SV2 ON, SV41, SV42 ON, Operation frequency limit
SV6 ON, Operation frequency limit
Operation frequency limit
Outdoor fan speed up, Operation frequency limit
69
Operation

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents