Toshiba R410A Service Manual page 162

Super heat recovery multi system
Hide thumbs Also See for R410A:
Table of Contents

Advertisement

Check code
Check code name
[–] / [97]
AI-NET communication line error
(TCC-L / AI-NET)
NO
Are AI-NET X and Y
communication lines normal?
YES
Are connections of CN01,
CN02, and CN03 connectors
NO
on network adaptor P.C. board
(MCC-1401) and CN309
and CN41 connectors on
indoor P.C. board normal?
YES
Are remote controller
NO
communication lines
(A, B) normal?
YES
YES
Is there no connection error
on the power line?
NO
YES
Is not main power supply
turned on?
NO
YES
Did a block-out occur?
NO
Is the network
YES
address changed by the main
remote controller?
NO
YES
Is there any noise etc.?
NO
Can other indoor units
be controlled from AI-NET
Unavailable (Others are same.)
central remote controller,
or is the operation status
of indoor unit the same?
YES
Can the
NO
Does the network adaptor
indoor unit be
P.C. board LED (D01) turn on?
controlled from the main
remote controller?
YES
YES
Cause of operation
AI-NET communication line error
Correct communication line.
Correct connection of connectors.
Check connection of A, B terminal.
Correct communication line of remote controller.
Correct power line.
Turn on the main power supply.
Clear check code.
Eliminate noise, etc.
®
Check central controller.
Failure
Replace
NO
®
Check indoor P.C. board.
Failure
Replace
Check power transformer of the
®
network adaptor P.C. board (MCC-1401).
Failure
Replace