Hitachi L700 SERIES Quick Reference Manual page 69

Hide thumbs Also See for L700 SERIES:
Table of Contents

Advertisement

Chapter 6 Specifications
(3) Common specifications of 200 V class and 400 V class models (continued)
Model name (type name)
SJ700-XXXFF2.FEF2,FUF2
Ambient
temperature,
storage
temperature(Note5)
, humidity
Vibration tolerance
(See Note 1.)
Installation
environment
Coating color
Feedback option
Digital input option
DeviceNet option
LonWorks option
Profibus-DP option
Other optional components
Note 1: The vibration tolerance was tested in compliance with JIS C60068-2-6:2010 (IEC 60068-2-6:2007).
Note 2: The insulation distance complies with the UL and CE standards.
Note 3: The applicable motor refers to Hitachi standard 3-phase motor(4-pole).when using other motors,care must be taken to
prevent the rated motor current(50/60Hz)from exceeding the rated output current of the inverter.
Note 4: Function "64(EMR)"cannot be assigned to input terminal 3 by an operation from the operator. The function is automatically
assigned to the terminal when slide switch SW1 is set to ON.
Note 5: The storage temperature refers to the short-term temperature during transport.
Note 6: The frequency command will equal the maximum frequency at 9.8V for input voltage 0 to 10VDC,or at 19.8mA for input
current 4 to 20mA.If this characteristic is not satisfactory for your application, contact your Hitachi sales representative.
Note 7: The analog voltage monitor and the analog current monitor are rough output values for analog meter connection.
The maximum output value might shift a little by the difference of the analog output circuit than 10V or 20mA.
Please inquire when there is a possibility that the inconvenience is caused.
Note8: As for the range of the speed change, the variation range is different according to the installation situation and the
characteristic and the usage condition of the motor. Please inquire about details.
Note9: The density of air decreases by 1% whenever rising by 100m when the altitude exceeds 1000m. Therefore, it is necessary to
decrease the calorific value. The calorific value of the main circuit semiconductor such as IGBT is proportional to the current
and the voltage. Therefore, please decrease by 1% and use the current rating every time it rises by 100m.
Please inquire about use in the high ground of 2500m or more.
110
150
185
220
L/H
L/H
L/H
L/H
-10°C to +40°C (ambient), -20°C to +65°C (storage), 20% to 90% RH (no condensation allowed)
2
5.9m/s
(0.6G),10~55Hz
Environment without corrosive gases and dust, at an altitude of 1,000 m or less Note9)
Gray
Vector control with sensor
4-digit BCD input, 16-bit binary input
Option to support the open-network DeviceNet function
Option to support the open-network LonWorks function
Option to support the open-network Profibus-DP function
Braking resistor, AC reactor, DC reactor, noise filter, operator cables, Harmonic-wave suppressor unit,
LCR filter, analog operation panel, regenerative braking unit, controllers for various applications
300
370
450
550
L/H
L/H
L/H
L/H
2.94m/s
6 - 4
750
900
1100
1320
L/H
H
H
H
2
(0.3G),10~55Hz
1600
H

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents