Safety Instructions
Precautions Concerning Compliance with UL and cUL Standards
(Standards to be met: UL508C and CSA C22.2 No. 14-05)
These devices are open type and/or Enclosed Type 1 (when employing accessory Type 1 Chassis Kit) AC
Inverters with three phase input and three phase output. They are intended to be used in an enclosure.
They are used to provide both an adjustable voltage and adjustable frequency to the ac motor. The inverter
automatically maintains the required volts-Hz ration allowing the capability through the motor speed range.
1. "Use 60/75 C CU wire only" or equivalent. For models L700 series except for L700-110H and
L700-150H.
2. "Use 75C CU wire only" or equivalent. For models L700-110H and L700-150H.
3. "Suitable for use on a circuit capable of delivering not more than 100 k rms symmetrical amperes,
240 V maximum". For models with suffix L.
4. "Suitable for use on a circuit capable of delivering not more than 100 k rms symmetrical amperes,
480 V maximum". For models with suffix H.
5. "Install device in pollution degree 2 environment".
6. "Maximum Surrounding Air Temperature 45 or 50°C".
7. "CAUTION- Risk of Electric Shock- Capacitor discharge time is at least 10 min."
8. "Integral solid state short circuit protection does not provide branch circuit protection. Branch circuit
protection must be provided in accordance with the NEC and any additional local codes."
9. "Solid state motor overload protection is provided in each model"
10. Tightening torque and wire range for field wiring terminals are in the table below:
Model No.
Required torque (N-m)
L700-110L
L700-150L
L700-185L
L700-220L
L700-300L
L700-370L
L700-450L
L700-550L
L700-750L
Model No.
L700-110H
L700-150H
L700-185H
L700-220H
L700-300H
L700-370H
L700-450H
L700-550H
L700-750H
L700-900H
L700-1100H
L700-1320H
L700-1600H
4.0
4.0
4.9
4.9
8.8
8.8
20.0
20.0
19.6
Required Torque (N.m)
4.0
4.0
4.9
4.9
4.9
4.9
20.0
20.0
20.0
20.0
20.0
35.0
35.0
Wire range (AWG)
2/0 or Parallel of 1/0
4/0 (Prepared wire only) or Parallel of 1/0
4/0 (Prepared wire only) or Parallel of 1/0
(Prepared wire only) or Parallel of 2/0 (Prepared wire only)
Wire Range (AWG)
Parallel of 1/0
Parallel of 1/0
Parallel of 3/0
Parallel of 3/0
iv
6
6-4
2
1
1 or 1/0
350 kcmil
10
8
6
6
6 or 4
3
1
1
2/0