1. General Specifications

Item
Rated voltage
100 to 240 V AC (AC power), 24 V DC (DC power)
Operating voltage range
85 to 264 V AC (AC power), 20.4 to 28.8 V DC (DC power)
Service power output
C14: 24V DC/0.15A, C30 and C60: 24V DC/0.4A
40 A or less (C14), 45 A or less (C30, C60) at 25°C (AC power)
Rush current
12 A or less at 25°C (DC power)
Allowed momentary power off time
10 ms or more
Ambient temperature
0 to +55°C
Storage temperature
-40 to +70°C
10 to 95% RH (at 25 °C, non-condensing)
Ambient humidity
10 to 95% RH (at 25 °C, non-condensing)
Storage humidity
Combined input/output terminals - Combined power and ground terminals,
2300 V AC*
Input terminals - Relay output terminals, 2300 V AC*
Breakdown voltage
Input terminals - Transistor output terminals, 500 V AC*
Power terminals - Ground terminals, 1500 V AC*
500 V AC*
Combined input/output terminals - Combined power and ground terminals,
100 MΩ or higher (500 V DC using an insulation resistance meter)
Insulation resistance
Input terminals - Output terminals, 100 MΩ or higher (500 V DC using an insulation resistance meter)
Power terminals - Ground terminals, 100 MΩ or higher (500 V DC using an insulation resistance meter)
5 to 9 Hz, single amplitude 3.5 mm/9 to 150 Hz, constant acceleration 9.8 m/s
Vibration resistance
1 sweep/min, 10 sweeps in each XYZ direction
147 m/s
Shock resistance
1500 V [P-P] pulse width 50 ns, 1 µs (AC power),
500 V [P-P] pulse width 50 ns, 1 µs (DC power)
Noise immunity
(per noise simulator method) (power terminals)
Operating condition
No corrosive gas and no excessive dust
EC Directive Compliance Standard
Conforming to EN61131-2
Level of contamination
2
Over-voltage category
II
*1 Cutoff current 5 mA
2. Power Consumption, Weight
Product name
Part number
AFPX-C14❍❍
Control Unit
AFPX-C30❍❍
AFPX-C60❍❍
AFPX-E16❍❍
Expansion I/O Unit
AFPX-E30❍❍
Expansion FP0 adapter
AFPX-EFP0
Input cassette
AFPX-IN8
AFPX-TR8
Output cassette
AFPX-TR6P
Pulse I/O cassette
AFPX-PLS
Master memory cassette
AFPX-MRTC
Analog input cassette
AFPX-AD2
Analog I/O cassette
AFPX-A21
Analog output cassette
AFPX-DA2
Thermocouple input cassette
AFPX-TC2
AFPX-COM1
AFPX-COM2
Communication
AFPX-COM3
cassettes
AFPX-COM4
AFPX-COM5
AFPX-COM6
*2 Power consumption by the AC power supply connected to the control unit
*3 Power consumption by the DC power supply connected to the expansion FP0 adapter
Please refer to the user manual and specifications for further details.
22
Description
1
1
1 minute (AC power), 500 V AC*
1 minute (DC power)
1
1 minute (AC power),
1
1 minute (DC power)
2
Current consumption
Weight
2
Approx. 280g or less
26W or less*
2
Approx. 490g or less
52W or less*
2
64W or less*
Approx. 780g or less
8W or less*
2
Approx. 195g or less
2
Approx. 470g or less
45W or less*
3
Approx. 65g
0.24W or less*
2
1W or less*
Approx. 25g
2
Approx. 25g
1W or less*
2
Approx. 25g
1W or less*
2
Approx. 25g
2W or less*
2
2W or less*
Approx. 20g
2
Approx. 25g
2W or less*
2
Approx. 25g
3W or less*
2
Approx. 25g
5W or less*
2
1W or less*
Approx. 25g
2
Approx. 20g
2W or less*
2
3W or less*
Approx. 25g
2
2W or less*
Approx. 20g
3. Controls Specifications
Item
Program method
Control method
Program memory
Program capacity
Operation processing speed
Basic instructions
Applied instructions
External inputs (X)
External outputs (Y)
Internal relay (R)
Special internal relay (R)
Link relay (L)
1
1 minute
1
1 minute
Timer/counter (T/C)
Data register (DT)
Link data register (LD)
Special data register (DT)
Index register (I0 to ID)
Master control relay (MCR)
2
,
Number of labels (LOOP)
Number of differentiations
Number of stepladders
Number of subroutines
Number of interruption programs
*5
High-speed counter
*6
Pulse output
Pulse catch input / interrupt input
Periodical interrupt
Potentiometer
Constant scan
Real-time clock
Backup by F12,
P13 commands
Flash ROM
*9
backup
Auto-backup
at power failure
Battery backup
Before installing
AFPX-MRTC
Battery life
After installing
AFPX-MRTC
(when no power
is supplied)
Password
Self-diagnosis function
Comment storage
PLC link function
Rewriting in RUN mode
*4 The actual usable number of points is restricted by the hardware.
*5 Specification at the rated input voltage of 24 V DC, 25°C. Frequency may be lower due to
the voltage and temperature.
*6 Max frequency may vary by the method of operation. Please refer to the manual for details.
*7 Calendar accuracy at 0°C: 119 sec/month or less, 25°C: 51 sec/month or less, 55°C: 148
sec/month or less (Real-time clock requires a battery.)
*8 When data is stored in the storage area while the battery is not installed, the data is not
cleared and the data value may be indefinite.
The same condition occurs when the battery is exhausted.
*9 The number of possible rewrites is 10,000 or less.
Specifications
Relay symbol method
Cyclic operation method
Flash ROM built-in (no battery backup required)
16 ksteps (C14), 32 ksteps (C30, C60)
Basic instruction 0.32 µs/step
111
216
*4
1760 points
*4
1760 points
4096 points
192 points
2048 points
Total 1024 points: timer capable of counting
(1 ms, 10 ms, 100 ms, 1 s) x 32767
Counter capable of counting 1 to 32767
12285 words (C14), 32765 words (C30, C60)
256 words
374 words
14 words
256 points
256 labels
Up to program capacity
1000 stages
500 subroutines
Relay output type: 15 programs (14 external, 1 constant)
Transistor output type: 9 programs (8 external, 1 constant)
Built-in (Transistor output): single-phase 8 ch (50 kHz x 4 ch + 10 kHz x 4 ch)
Built-in (Relay output): single-phase 8 ch (10 kHz x 8 ch)
Pulse I/O cassette: single-phase 2 ch (80 kHz x 2 ch)
Built-in (Transistor output): 100 kHz x 2 ch + 20 kHz x 2 ch
Pulse I/O cassette: One unit (one axis) 100 kHz, or two units (two axes) 80 kHz
Relay output type: Total 14 points (including the high-speed counter)
Transistor output type: Total 8 points (including the high-speed counter)
0.5 ms to 30 s
2 points (0 to 1000) (C14, C30) 4 points (0 to 1000) (C60)
Possible
Equipped (usable only when AFPX-MRTC is installed)
Data register (32765 words)
Counter 16 points (1008 to 1023), Internal relay 128 points
(R2470 to R255F), Data register 55 words
The memory allocated in the storage area by the
system register (only when a battery is installed)
C14: 1230 days (actual operation 10 years at 25°C)
C30, C60: 990 days (actual operation 10 years at 25°C)
C14: 780 days (actual operation 10 years at 25°C)
C30, C60: 680 days (actual operation 10 years at 25°C)
(More than two batteries can be installed in C30 and C60.
In this case, the battery life is extended several times)
Capable (4 or 8 characters selectable)
Watch dog timer, program syntax check
Capable (328 KB) (backup battery not required)
Max 16 units, link relay 1024 points, link register 128 words
(No data transfer or remote programming)
Capable
*7
*8

Hide quick links:

Advertisement

Table of Contents
loading