To set the point mode of the RF Transmitter, see Section 3.6.1.1 Point Mode, p.17 for information on
5.
selectable Point Modes.
After the Mode is selected, the keypad will display the available
6.
check-in time selection of either 1 minute (by pressing [1] +
[ENT]) or 5 minutes (by pressing [2] + [ENT]).
Enter the desired check-in time and press [ENT].
The check-in time is a supervisory signal that is sent from each
transmitter at this interval. Each transmitter shipped from
Inovonics comes defaulted with a 1 minute check-in time. To
extend battery life of the transmitter, this entry may be set to the
5 minute interval. For fire, set the entry to one minute.
After the check-in time is entered, the D8125INV will display the
7.
following.
Push [3] to continue adding the transmitter
8.
The keypad displays two options:
9.
Push [1] for a new transmitter
Push [2] for an existing transmitter
Press [1] on the keypad