Controls - Zeta Premier EX8 User Manual

Combined fire & extinguishing control panel complies with bs en 12094 part 1 & en54 parts 2 & 4
Hide thumbs Also See for Premier EX8:
Table of Contents

Advertisement

Extinguishing Panel - USER MANUAL

Controls

The Premier EX8 has the following controls:-
LABEL
USE
st
START/STOP 1
Used to silence the sounders in an alarm, or to manually start the FIRST
STAGE SOUNDER
STAGE sounders to evacuate building
SILENCE BUZZER
Used to silence the panel`s internal buzzer in a fault or alarm condition.
RESET FIRE
Used to reset the Fire detection section of the Control panel (Ie Zones 1 to 6)
PANEL
RESET
Used to Reset the extinguishing section of the Control panel.
EXTINGUISHING
SYSTEM
LED TEST
To check that all indicator LEDs are working. Use as part of the daily / weekly
fire alarm inspection.
DISABLE
Used to access Disablement mode
DISABLE –
Used to scroll to select which part of the system to disable
SELECT
DISABLE –
Used to confirm disablement of the highlighted part of the system.
CONFIRM
TEST
Used to access test mode
TEST – SELECT
Used to scroll to select which part of the system to test
TEST – CONFIRM
Used to confirm test mode of the highlighted part of the system.
AUTO / MANUAL
Used to toggle between automatic & manual only mode
GAS RELEASE
Used to view or alter Gas Release Counter
COUNTER
RELEASE
Used to view or alter Release Duration Time Counter
DURATION TIME
RESET INHIBIT
Used to view or alter Reset Inhibit Time Counter
TIME
0-9
To enter access code & timer values
ENTER
To confirm new timer setting
CANCEL
To Save an edited time and exit from the timer set-up.
TERMINATE
Used to terminate the release duration timer (Bottle output Active). Internal
DURATION TIMER
button. Used during commissioning only.
Note that the controls can only be used after the keyswitch has been turned to the
CONTROLS ENABLED (ON) position.
As the Premier EX8 is a combined Extinguishing & fire alarm control panel, it is
possible that both the extinguishing section, and the fire alarm section are in alarm at
the same time. If this occurs, the reset Fire Panel button can be used to reset the
Zone alarms, leaving the extinguishing section active. After the pre-programmed
Reset Inhibit delay, the reset Extinguishing System button can then be used to reset
the extinguishing section.
If the Extinguishing system has been through it`s release cycle, and the zones that
triggered the release are still in alarm, the reset fire panel button must be pressed
first to reset the zones in alarm, before the reset extinguishing system button can be
pressed.
Approved Document No: GLT.MAN-132
Issue : 1.2
Author: NRPJ
Date: 06/10/2010
PAGE 6