Extinguishing Panel - USER MANUAL

INTRODUCTION

The Premier EX 8 is a combined 2 zone , 1 area extinguishing panel, and 4 zone
conventional fire alarm panel.
It has 2 zones dedicated to the extinguishing section. These are known as crossed or
co-incidence zones. Both circuits will need to be triggered in order to activate the
extinguishing circuit. This kind of operation also referred to as "double – knock"
It has 4 zones for fire detection (referred to as peripheral zones, or fire zones). These
will not trigger the extinguishing circuit.
The Extinguishing section is designed to BSEN12094-1:2003.
The fire alarm section is designed to EN54-2:1998 A1 + A2.
The Power Supply section is designed to EN54-4:1998 A1 + A2
This design allows the same panel to protect an extinguishing area, and also monitor
the rest of the site for a fire.
The panel has an integral Manual Release call point fitted to the front of the panel.
The panel has monitored inputs for field connections, such as manual release,
emergency hold, etc.
The panel has relay outputs for first & second stage alarms, fault & gas fired.
The panel has remote inputs for Start/Stop Sounders, Silence & Reset, to allow the
panel to be controlled remotely.
The panel has Open collector repeat outputs for most panel status indications (eg 1
nd
stage alarm, 2
stage alarm, Automatic mode, Manual mode etc)
The panel has a connection for a serial repeater unit (4 wire)
The Premier EX8 can be in any of the following conditions:-
Quiescent condition – ie System Normal
Fire condition – ie a fire on one of the peripheral zones
o The Premier EX8 will enter the fire condition within 1 second of a
detector on a peripheral zone signalling an alarm.
Fault condition
Disabled condition
Test condition
Pre-activated condition
o The Premier EX8 will enter the pre-activated condition (first stage
alarm) within 1 second of a detector on one of the crossed zone
signalling an alarm.
Activated condition
o The Premier EX8 will enter the activated (second stage alarm)
condition within 1 second of the second crossed zone signalling an
alarm.
Released condition
o The Premier EX8 will enter the released condition (bottle output
activated) within 1 second of establishing the activated condition, OR
after the delay configured in the bottle output timer.
WARNING: Access to live components inside this fire alarm enclosure. The key
to open the door to gain internal access should be held by authorised
personnel only.
Approved Document No: GLT.MAN-132
Issue : 1.2
Author: NRPJ
Date: 06/10/2010