Part X: set PIn access For servIce menUs (oPtIonal)
Creating a PIN access code allows the installer to restrict access to Service Menus. First,
a PIN access must be enabled in Service Menu 341; second, a three-digit code must be
created in Service Menu 342. After these two Service Menus are properly confi gured, the
thermostat requires the user to enter a PIN access code to enter the Service Menus.
1. On the thermostat, press the lower left and lower right keys simultaneously for about
fi ve seconds. Next,
Back, and
Go
2. Press
until Service Menu 341 (Enable/Disable PIN Access) appears in the
Next
display. (Default value appears below Service Menu.)
Figure 15.
Service Menu
341 allows
user to restrict
access to
Service
Menus.
3. In Service Menu 341, press ▲/ ▼to change digit (fl ashing) value to "01" (see Fig. 16).
note: selecting 01 enables PIn access for the thermostat service menus, and
selecting it is necessary to show service menu 342.
4. Press Next.
5. In Service Menu 342, press ▲/ ▼adjust values and create a three-digit PIN access
code. The fl ashing three-digit code appears in the clock area (see Fig. 16).
note: write down the PIn access code, and keep it in a safe place.
Figure 16.
Service Menu
342 allows
user to create
a PIN access
code.
6. Press
when fi nished.
Done
verIFY PIn access coDe
Enter the PIN access code upon entering the Service Menus. Note: Flashing digit is active;
it is changed using the ▲/ ▼keys. The active (editable) digit moves from right to left.
1. On the thermostat, press the lower left and lower right keys simultaneously for about
fi ve seconds. note: Flashing three-digit code, Next, and
2. Press ▲/ ▼to change value of digit furthest to the right, then press Next.
3. Press ▲/ ▼to change value of digit in middle, then press Next.
4. Press ▲/ ▼to change value of digit furthest to left, then press Done.
note: After step 4 is complete, user is allowed access to Service Menus. Next,
and Service Menu 100 appear.
Go
Back,
Done,
Figure 17.
PIN access
code fl ashes
when user
enters Service
Menus (after
enabling PIN
access).
© COPYRIGHT 2010 PECO, INC. ALL RIGHTS RESERVED.
appear (see Fig. 15).
Done
Flashing
three-digit
code
appear (see Fig. 17).
Done
Flashing
three-digit
code
t8000 serIes PerFormance Pro accessorIes: sensors
The following T8000 Series compatible sensors are available from PECO, providing
optimal control of the environment. In addition, following are sensor wiring diagrams for
temperature averaging, Indoor Remote Zone Sensor installation instructions, and Outdoor
Remote Sensor installation instructions.
Peco sensors
model
number
SP155-017
Indoor Remote
Sensor
SB200-001
Occupancy Sensor
--
Outdoor Remote
Sensor
To learn more about the benefi ts of PECO sensors visit www.pecomanufacturing.com.
Or call 1-800-874-8547 to speak with a service representative.
taBle 4. Zone sensor maXImUm lenGth anD wIre sIZe
Distance from Unit to control
000 - 150 feet
151 - 240 feet
241- 385 feet
386 - 610 feet
611 -970 feet
note:
Use appropriate wire for outdoor use.
locate & moUnt Peco occUPancY sensor (sB200-001)
Please use the installation instructions for the SB200-001 to mount the PECO Occupancy
Sensor SB200-001.
sensor wIrInG For temPeratUre averaGInG
9
Part
terminal
t8000
t8500
number
69308
S1
68375
S2
70327
S3
recommended wire size
22 gauge
20 gauge
18 gauge
16 gauge
14 gauge
Wiring four SP155-017
(10K ohm) temperature sensors.
Wiring nine SP155-017
(10K ohm) temperature sensors.
P/N 70413 3220-2260 REV 01
Figure 18.
Figure 19.

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Performance pro t8000 series

Table of Contents