Control Expression; Trigger Conditions - Panasonic MEW01 351 Planning Manual

Fire alarm system
Table of Contents

Advertisement

Panasonic Electric Works Nordic AB
MEW01351
Rev: -
13.5
13.5.1
Planning Instructions Fire alarm system EBL512 G3, V1.1.x

Control expression

Each programmable output has to be given a control expression. It is
created by so called Boolean algebra.
Trigger conditions (see "Available functions"), logical "Operators"
(AND, OR, NOT) and parentheses are used to make a "control
expression" containing up to 40 trigger conditions. See also chapter
"Control expression examples" page 80 and WinG3 help.
A programmable output will be activated as long as its control
expression is true.
Figure 15.
In any output dialog box, click the right mouse
button in the large white field to show a "Trigger conditions list".
Depending
on
the
arguments / data have to be entered.

Trigger conditions

Some trigger conditions require additional information, see
information within parentheses (+nnnnn) after the trigger condition
respectively below.
The following trigger conditions are available (numbering only for the
comments below):
1
Fire Alarm Zone (+Zone no.)
2
Fire Alarm Zone Address (+Zone no.+Address)
3
General Fire Alarm
4
Consecutive Fire Alarm (sequence) (+start Zone no. and
address +stop Zone no. and address +Quantity)
5
Pre Warning Zone (+Zone no.)
6
Pre Warning Zone Address (+Zone no.+Address)
7
General Pre Warning
8
Consecutive Pre Warning (+start Zone no. and address
+stop Zone no. and address +Quantity)
selected
trigger
condition,
76
different

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ebl512 g3

Table of Contents