11.1
Planning Instructions Fire alarm system EBL512 G3, V1.1.x

Input programming

Input programming is done in WinG3. For more information see
WinG3 help. Each input has to have an individual Trigger condition
("Triggered by") and Logic. It is not recommended to let two or more
inputs have the same trigger condition.

Trigger conditions

The following trigger conditions are available (numbering only for the
comments below):
0. Activate output
1. Activated fault routing equipment (one input per C.U.)
2. Activated key cabinet
3. Activated Routing Equipment (one input per C.U.)
4. Alarm Key Cabinet (one input per control unit)
5. Alert Annunciation Acknowledge
6. Alert Annunciation Reset
7. Door Closing Test Input
8. Evacuate (one input per C.U.)
9. External Fault (50 inputs per system)
10. External Time Channel (one input per time channel 15-63 per
system)
11. Extinguishing alarm
12. Extinguishing system fault
13. Extinguishing system released (one input per C.U.)
14. Fault Signal External Fuses (one input per control unit)
15. Fault Signal External Power Supply (one input per control unit)
16. Fault warning routing equipment fault
17. General Fire (max. 127 per C.U.)
18. Interlocking (200 inputs per C.U. / 1000 per system)
19. Loss of battery charger to external power supply (one input per
C.U.)
20. Loss of main power source to external power supply (one input
per C.U.)
21. Not used
22. Pre-warning (input and corresponding fire alarm input have to be
"connected" to the same C.U.)
49
23. Silence alarms
(one input per system)
50
24. Zone Line Input
49
Only valid for the New Zealand convention.
50
Only valid for the Addressable multipurpose I/O unit 3361 input "In0",
used as zone line input (Z).
64