Limitations; User Definable Texts; C.i.e. / System - Panasonic MEW01 351 Planning Manual

Fire alarm system
Table of Contents

Advertisement

Panasonic Electric Works Nordic AB
MEW01351
Rev: -
28
28.1
28.2
Planning Instructions Fire alarm system EBL512 G3, V1.1.x

Limitations

See also "Control Unit / TLON Network", page 17.

User definable texts

At least 617 "User definable texts" can be programmed per c.i.e. The
texts are to be distributed amongst the following:
Alarm text for Alarm points (Zone / Address)
Alarm text for Alarm Zones
Interlocking Combinations
Ext. faults
At least 617 "User definable texts" can be programmed per 1728,
1735, 1736, 1826 and 1828 unit.

C.i.e. / System

Max. number of "items" for the system is the same as per C.i.e. if
nothing else is specified:
......table on following page...
160