Special New Zealand Functions; Alarm Devices; Silence Alarm Devices (Inside Switch); New Zealand Fb Silence Switch (Outside Switch) - Panasonic MEW01 351 Planning Manual

Fire alarm system
Table of Contents

Advertisement

Panasonic Electric Works Nordic AB
MEW01351
Rev: -
17
17.1
17.1.1
17.1.2
Planning Instructions Fire alarm system EBL512 G3, V1.1.x

Special New Zealand functions

NOTE! The functions in this chapter are valid for the New Zealand
convention only.

Alarm devices

Silence alarm devices (inside switch)

On the c.i.e. front, the button "Silence alarm devices" (see Operating
Instructions MEW01163, button "P2") is called the "inside switch"
and toggles between two states:
 Alarm devices disabled
All programmable outputs of type "Alarm devices" are
disabled, i.e. they cannot be activated.
 Alarm devices not disabled
All programmable outputs of type "Alarm devices" enabled,
i.e. they can be activated.
If the inside switch is in its disabled state when you are closing the
c.i.e. door the buzzer will beep once and the message "Silence
switch left active" will be shown in the display.
message has lower priority than fire alarms but higher than other
disablements and faults.
NOTE! The inside switch has no function if the outside switch (see
below) is activated (on).

New Zealand FB Silence switch (outside switch)

The "New Zealand FB Silence switch" is called the "outside switch"
since it is placed outside the c.i.e. The outside switch is a key switch
and is connected to a programmable input with the trigger condition
"Silence alarms".
The outside switch is turned ON (i.e. from not activated to activated
state).
 All programmable outputs of type "Alarm devices" are
115
disabled
, i.e. they cannot be activated. The "inside switch"
(see above) has no function.
 LEDs "Fire" (on the c.i.e. front) changes from blinking to
steady (continuous).
 The c.i.e. built-in buzzer is silenced.
 A fault is generated
active, control unit xx
115
Indicated by LED "General disablements" on the c.i.e. front.
116
This is valid also if the fire alarm is activated after the outside switch is
turned on.
117
116
117
: "FAULT: FB Silence switch
"
This

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ebl512 g3

Table of Contents