Planning Instructions Fire alarm system EBL512 G3, V1.1.x
NOTE! If any alarm point shall have a different alarm text in one or
more of the "display units" 1826, 1828, 1735, 1736 or 1728
has to be typed in the WinG3 "Text editor", for the "display unit"
respectively (Properties | Edit texts...):
Explanations (Text editor for one specific "display unit"):
Zone-Address column
Shows the already programmed alarm points (e.g. 001-01, 001-02,
002-01 etc.).
Shows the already programmed zones, i.e. I/O unit 3361 zone line
inputs programmed with address "00" (i.e. as ZZZ – 00) and 8 zones
expansion board 4580 zone line inputs.
Text in control unit column
Shows already programmed alarm texts for each alarm point / zone.
This is information only and cannot be edited. These texts will be
displayed in the c.i.e. and all "display units" 1826, 1828, 1735, 1736
and 1728 if there are no other texts programmed in the "Text column".
Text column
The text to be shown in this "display unit" for the alarm point / zone
respectively, has to be typed (edited) here. NOTE! In this "display
unit" this text will now be shown instead of the text in the "Text in
control unit" column, for the alarm point / zone respectively.
Downloading alarm texts to the DU:s 1728 / 1735 /
1736 and ext. FBP:s 1826 / 1828
The texts will be downloaded when the site specific data (SSD) is
downloaded via WinG3.
The unit respectively has to be set in S/W mode xxxx – 1587

Real time clock (RTC)

Each control unit has an RTC.
presentation for fire alarms, faults, event logging and the time
channels 2-14. In a system with two or more control units in a TLON
network is the time in all control units synchronised.
110
Regarding text priority order etc. see Technical Description (chapt. "User
definable text messages") for the "display unit" respectively.
111
The calendar and clock can be set in any c.i.e. for the whole system.
Every day (at midnight) all calendars and clocks will be synchronised.
113
110
It is used for (date) and time
111