Planning Instructions Fire alarm system EBL512 G3, V1.1.x

Programmable inputs

In each control unit are four programmable, not supervised inputs
(I0-I3) available.
In EBL512 G3 can also be mounted the Inputs and Outputs expansion
board 4583, with five programmable inputs (Input 0-4). See chapter
"Expansion boards 458x", page 26. These inputs can be supervised or
not supervised.
On the COM loops can be connected the addressable multipurpose I/O
unit 3361 with two programmable inputs.
Each input is programmed (via WinG3) regarding:
Name (Normally not changed, but used as Interlocking input it is
recommended to add some identity information)
Logic, Normally open (high resistance, 3K3, when supervised) or
Normally closed (low resistance, 680R, when supervised)
Not supervised or Supervised. (Not valid for 3361.)
Triggered by ("Trigger condition")
The following depending on selected trigger condition:
Fault number
Fault text ("Fault message")
Zone no. - Address
Text ("Alarm text")
Time channel no.
COM loop address
Output no.
Figure 10.
WinG3 "Input" dialog boxes.
conditions require different additional information, i.e. only not
disabled fields can/shall be filled in.
NOTE! The 3361 unit, Input 0, has a special input dialog box.
62
Different trigger