Panasonic Electric Works Nordic AB
MEW01351
Other units
Routing equipment (Fire brigade tx / Fault tx)
External Presentation unit 1728
Alert Annunciation unit 1735 / 1736
External FBP 1826 / 1828
Printer 1835 (for ext. FBP 1826)
Alarm devices (sounders, etc.)
Door release magnets
Alert annunciation controller 1740
Rev: -
Planning Instructions Fire alarm system EBL512 G3, V1.1.x
NOTE! Regarding the 1728, 1735, 1736, 1826, 1828 and 1835 units,
see the next page.
137
When the printer is active the current consumption is 161 / 345 mA
momentarily.
Normal state
(quiescent) (mA)
Acc. to the producer
26@24 V / 48@12 V
26@24 V / 48@12 V
26@24 V / 48@12 V
137
4@24 V / 7@12 V
0
Acc. to the producer
10
150
Alarm state
(activated) (mA)
Acc. to the producer
49@24 V / 88@12 V
42@24 V / 79@12 V
49@24 V / 88@12 V
4@24 V / 7@12 V
Acc. to the producer
0
40