Wing3 Control Unit Pop-Up Menu; Reset Alarm Counter; Software Version; Upgrade Number Of Alarm Points - Panasonic MEW01 351 Planning Manual

Fire alarm system
Table of Contents

Advertisement

Panasonic Electric Works Nordic AB
MEW01351
Rev: -
19.2
19.2.1
19.2.2
19.2.3
Planning Instructions Fire alarm system EBL512 G3, V1.1.x
Set the wanted number and the validation check in WinG3 can give a
"too many alarm points" warning.
automatically performed when starting a download of SSD to the c.i.e.
Suppress buzzer during fault: This check box shall be marked
if faults generated in other control units shall be suppressed in this
control unit, i.e. if the buzzer shall sound for faults generated in
this control unit only.
Use Pre-warning: This check box shall be marked if the pre-
warning detection shall be enabled, i.e. pre-warnings will be
activated in this control unit and presented in all control units. All
programmable outputs in the system, with trigger condition "Pre-
warning", will be activated (if not disabled).
Checkbox not marked = Pre-warnings will not be activated in this
control unit.

WinG3 Control unit pop-up menu

Some commands might be disabled since you have to connect and log
on to the control unit to be able to select / use them.

Reset alarm counter

The control unit has an alarm counter that can be reset if required.

Software version

The control unit software (S/W) version will be displayed.

Upgrade number of alarm points

The control unit is by delivery be configured for 128, 256 or 512
alarm points. Any number of alarm points can be changed on site,
normally 128  256  512.
129
The validation check is