Figure 3.7.1 Power And Control Wire Connections For 4 Units In Mms (80-225Kva) - Toshiba G9000 SERIES Installation And Operation Manual

480/480 v 80/100/160/225/300/500/750 kva
Hide thumbs Also See for G9000 SERIES:
Table of Contents

Advertisement

FIGURE 3.7.1 Diagram of Power Wire & Control Wire Connections for 4 units in MMS Configuration
Use Ethernet STP
(Shielded Twisted
Pair) Cable (Cat 5 or
Cat 6) with RJ45
modular connectors
for all communication
cabling.
Use of UTP
(Unshielded Twisted
Pair) Cable may
Total cable length
from UPS-1 to UPS-n
should be within
100m.
*1 Return from the last
UPS module to the first UPS
module (continuous loop).
*2 DIP switch position
UPS-1 and UPS-n (n=2-4): ON
Otherwise : OFF
G9000 Installation and Operation Manual
(80-225kVA)
UPS-1
IFAU-08
CN96
TLIN
*1
CN95
TLOUT
CN94
CBIN
CBOUT
CAIN
CAOUT
*2
ON
UPS-2
IFAU-08
CN96
TLIN
CN95
TLOUT
CN94
CBIN
CBOUT
CAIN
CAOUT
*2
OFF
UPS-3
IFAU-08
CN96
TLIN
CN95
TLOUT
CN94
CBIN
CBOUT
CAIN
OUTPUT
CAOUT
*2
OFF
UPS-4
IFAU-08
CN96
TLIN
CN95
TLOUT
CN94
CBIN
CBOUT
CAIN
CAOUT
*2
ON
IOAU-09
TN1
5
6
AC
OUTPUT
A50
B50
C50
IOAU-09
TN1
5
6
AC
OUTPUT
A50
B50
C50
IOAU-09
TN1
5
6
AC
A50
B50
C50
IOAU-09
TN1
5
6
AC
OUTPUT
A50
B50
C50
Toshiba Tie Cabinet (TTC)
43
52L1-AX
44
45
52L2-AX
46
47
52L3-AX
48
49
52L4-AX
50
AC OUTPUT
UPS-1
A
B
C
UPS-2
A
B
C
UPS-3
A
B
C
UPS-4
A
B
C
63