Figure 3.7.2A Power And Control Wire Connections For 2 Units In Mms (300-750Kva) - Toshiba G9000 SERIES Installation And Operation Manual

480/480 v 80/100/160/225/300/500/750 kva
Hide thumbs Also See for G9000 SERIES:
Table of Contents

Advertisement

FIGURE 3.7.2a Diagram of Power Wire & Control Wire Connections for 2 units in MMS Configuration
Use Ethernet STP
(Shielded Twisted
Pair) Cable ( Cat 5 or
Cat 6) with RJ45
modular connectors
for all communication
cabling.
Use of UTP
(Unshielded Twisted
Pair) Cable may
cause malfunction.
Total cable length
from UPS-1 to UPS-2
should be within
100m.
*1 Return from the last
UPS module to the first UPS
module (continuous loop).
*2 DIP switch position
UPS-1 and UPS-2 : ON
64
(300-750kVA)
UPS-1
IOAU-09
IFAU-09
CN99
TLBIN
*1
CN98
TLAIN
*1
CN97
TLBOUT
CN96
TLAOUT
*2
ON
CN954
CB2IN
CN953
CB1IN
CN952
CA2IN
CN951
CA1IN
CN944
CB2OUT
CN943
CB1OUT
OUTPUT
CN942
CA2OUT
A50
CN941
B50
CA1OUT
C50
*2
ON
UPS-2
IOAU-09
IFAU-09
CN99
TLBIN
CN98
TLAIN
CN97
TLBOUT
CN96
TLAOUT
*2
ON
CN954
CB2IN
CN953
CB1IN
CN952
CA2IN
CN951
CA1IN
CN944
CB2OUT
CN943
CB1OUT
OUTPUT
CN942
CA2OUT
A50
CN941
B50
CA1OUT
C50
*2
ON
TN1
5
6
Toshiba Tie Cabinet (TTC)
47
48
49
50
AC
TN1
5
6
AC
G9000 Installation and Operation Manual
52L1-AX
52L2-AX
AC OUTPUT
UPS-1
A
B
C
UPS-2
A
B
C

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents