Toshiba G9000 SERIES Installation And Operation Manual page 48

480/480 v 80/100/160/225/300/500/750 kva
Hide thumbs Also See for G9000 SERIES:
Table of Contents

Advertisement

Details of input contacts for remote access : TN1
Terminals 7 to 8
Used to start inverter from a remote location. UPS must be programmed for remote
operation. Refer to Operations Menu for procedure.
Terminals 9 to 10
Used to stop inverter from a remote location. UPS must be programmed for remote
operation. Refer to Operations Menu for procedure.
Terminals 11 to 12 "Battery Temp. High" contact input (IN3)
Input fed by a thermocouple that monitors battery temperature. The converter float
voltage level is reduced for battery over-temperature conditions. External
thermocouple is user supplied
Terminals 13 to 14 "Power Demand" Command contact input (IN4)
This contact is used to control the input power. Power demand is turned ON when
the contact is closed, and power demand is turned OFF when the contact is open.
(The Power demand function is custom designed by the factory to match the users
specific system specifications. Contact the factory for additional information.)
Terminals 15 to 16 "Remote EPO" contact input
Used to perform a remote UPS Emergency Power Off (EPO).
The load will be dropped.
!
The UPS is equipped with a selectable input contact item.
The above items are the default settings.
Contact Toshiba International Corporation for setup information.
NOTE
In all cases, a switch having a protective cover is recommended in order to reduce
the possibility of accidental operation.
CAUTION
38
Remote "Inverter Start" input terminal (IN1)
Remote "Inverter Stop" input terminal (IN2)
G9000 Installation and Operation Manual

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents