Table 8
Liebert PSI XR battery run times (continued)
Number of Batteries
Internal battery
+ 4 External
Battery Cabinets
Internal battery
+ 5 External
Battery Cabinets
Internal battery
+ 6 External
Battery Cabinets
Run times are in minutes, assume fully charged batteries and are typical at 77°F (25°C) with resistive loads.
Load %
1000
10
790
20
494
30
360
40
283
50
233
60
198
70
172
80
152
90
137
100
124
10
965
20
605
30
440
40
346
50
265
60
242
70
211
80
186
90
167
100
151
10
1140
20
714
30
520
40
408
50
337
60
286
70
249
80
220
90
197
100
179
25
Specifications
1500
2200
627
483
371
303
264
221
204
174
167
143
141
122
122
106
108
94
96
79
82
72
762
564
452
354
320
258
248
203
203
167
171
142
148
124
131
110
117
98
106
84
897
644
531
405
377
295
292
232
239
191
202
163
175
142
154
125
138
112
124
102
3000
330
204
148
116
95
76
66
59
52
48
392
243
176
138
113
96
79
70
62
56
454
281
204
160
131
112
97
81
72
65