The following WARNING applies to battery cabinets supplied with UPS sysems: INTERNAL BATTERY STRAPPING MUST BE VERIFIED BY MANUFACTURER PRIOR TO MOVING A BATTERY CABINET FROM ITS INITIAL INSTALLATION LOCATION. Battery cabinets contain non-spillable batteries. Keep units upright. Do not stack. Do not tilt.
Page 3
MPORTANT AFETY NSTRUCTIONS Save These Instructions.
Page 13
Figure 1 Npower UPS modules, left-to-right: 30-50 kVA, 65-80 kVA and 100-130 kVA Installation Considerations...
Page 14
NLOADING AND ANDLING • Cut the metal banding straps and remove. • Unbolt and remove the four corner brackets retaining the 2x4 boards. • Use forklift to remove module from pallet. Unloading and Handling...
Figure 2 Front view, Npower UPS module on pallet BAND USING POLYP. PLASTIC BANDING (3) PLACES BAG PLASTIC COVER UNDER CARDBOARD CORRUGATED # 72 CARDBOARD NOT SHOWN Figure 3 Top view, Npower UPS module on pallet (2) 2 X 4 X 33" LG CARDBOARD SHEET METAL BANDING 3/4"...
Page 19
Battery Safety Precautions in French Per CSA Requirements Instructions Importantes Concernant La Sécurité Conserver Ces Instructions Battery Installation...
Page 23
ONFIGURING EUTRAL AND ROUND ONNECTIONS Configuring Your Neutral and Ground Connections...
Page 24
Figure 4 Grounding Diagram, A/B or G/H UPS Models, Wye Source, 3-Wire Loads Grounding for A/B or G/H UPS Models, Wye Source, 3-Wire Loads Configuring Your Neutral and Ground Connections...
Page 25
Figure 5 Grounding Diagram, A/B or G/H UPS Models, Wye Source, 4-Wire Loads Grounding for A/B or G/H UPS Models, Wye Source, 4-Wire Loads Configuring Your Neutral and Ground Connections...
Page 26
Figure 6 Grounding Diagram, D/E or K/L UPS Models, Delta or Wye Source, 4-Wire Loads Grounding for D/E or K/L UPS Models, Delta or Wye Source, 3- or 4-Wire Loads Configuring Your Neutral and Ground Connections...
Page 27
Figure 7 Grounding Diagram, R/S or X/Y UPS Model, Delta Source, 3-Wire Loads Grounding for R/S or X/Y UPS Models, Delta Source, 3-Wire Loads Configuring Your Neutral and Ground Connections...
Page 28
Figure 8 Grounding Diagram, A/B or G/H UPS Models, 1+1 Configuration A/B CONFIGURATION 4W+G 3W+G A/B CONFIGURATION 4W+G 3W+G Grounding for A/B or G/H UPS Models, 1+1 Configuration Configuring Your Neutral and Ground Connections SYSTEM PARALLELING CABINET 4W+G 4W+G 3 OR 4W+G CRITICAL LOAD...
Page 29
Figure 9 Grounding Diagram, D/E or K/L UPS Models, 1+1 Configuration D/E or K/L CONFIGURATION 3W+G 3W+G D/E or K/L CONFIGURATION 3W+G 3W+G Grounding for D/E or K/L UPS Models, 1+1 Configuration 4W+G 4W+G Configuring Your Neutral and Ground Connections SYSTEM PARALLELING CABINET 3 OR 4W+G CRITICAL...
Page 30
Figure 10 Grounding Diagram, R/S or X/Y UPS Models, 1+1 Configuration R/S or X/Y CONFIGURATION 3W+G 3W+G R/S or X/Y CONFIGURATION 3W+G 3W+G Grounding for R/S or X/Y UPS Models, 1+1 Configuration Configuring Your Neutral and Ground Connections 4W+G 4W+G SYSTEM PARALLELING CABINET 3W+G ONLY LOCAL...
Page 31
Grounding for 2 Npower UPS Modules feeding a Static Transfer Switch Grounding Configurations, Battery Systems Configuring Your Neutral and Ground Connections...
Page 36
IRING ONNECTIONS DC power cables (and ground) from Battery Cabinet to UPS Module, and between Battery Cabinets. Wiring Connections...
Page 37
Observe polarity. DC power cables should be installed in matched pairs (positive and negative). Wiring Connections...
Page 38
10.0 W IRING NSPECTION Table 1 Power Wiring Terminals - Factory Supplied UPS Module Rating 30-130 kVA Use 75°C copper wire. Select wire size based on the ampacities in Table 310-16 (see Table 3 of this manual) and associated notes of the National Electrical Code (NFPA 70). Use commercially available solderless lugs for the wire size required for your application.
Page 39
Table 3 Table 310-16 Allowable Ampacities of Insulated Conductors Rated 0-2000 Volts, 60° to 90°C (140° to 194°F) Not More than Three Conductors in Raceway or Cable or Earth (Directly Buried), based on Ambient Temperature of 30° (86°F) Size Temperature Rating of Conductor. See Table 310-13. 60°C 75°C (140°F)
Page 40
11.0 I NSTALLATION RAWINGS Figure 11 Outline Drawing, 30-50 kVA UPS Installation Drawings...