Siemens NCM S7 Manual page 163

Simatic net ncm for industrial ethernet
Table of Contents

Advertisement

How the Block Works
The following diagram illustrates the normal sequence of data acceptance
triggered by an AG_RECV in the user program.
Each AG_RECV job in the user program is acknowledged by the Ethernet CP with
an entry in the output parameters NDR, ERROR and STATUS.
User program
(CPU cycle)
Accept / evaluate
received data "A"
Accept / evaluate
received data "B"
Legend:
1) Parameter transfer NDR, ERROR, STATUS
The status code is updated at each block call.
SIMATIC NET NCM S7 for Industrial Ethernet
C79000-G8976-C129–06
Programming FCs (Functions) and FBs for S7 Ethernet CPs
Ethernet CP
AG_RECV
1)
0, 1, 8180
AG_RECV
1)
1, 0, 0000
AG_RECV
1)
0, 0, 8180
AG_RECV
1)
1, 0, 0000
AG_RECV
.
.
.
Time
Communications Partner
Transfer
"A"
active on
Ethernet
Transfer
"B"
active on
Ethernet
Transfer
"C"
active on
Ethernet
Time
Time