Room airconfitioner split wall-mounted type (36 pages)
Summary of Contents for Midea MSH-07CRN1, MSH-07HRN1, MSH-09CRN1, MSH-09HRN1, MSH-12CRN1, MSH-12HRN1
Page 1
CONTENTS 1. DIAGNOSTIC CHART 1 2. The service rules of the R407C(R410a) product 5 3. BRIGHT STAR SERIES 8 4. BRIGHT ECO SERIES 45 5. GLORY (ECO)STAR SERIES 65 6. GLORY GIANT 1 97 7. GLORY GIANT 2 115 8. LIGHT STAR SERIES 127 9.
Page 13
WINTER OUTDOOR CONDITIONS 12ºC D 7ºC D 4ºC D 0ºC D -4ºC D -7ºC D Indoor Conditions 11ºC W 6ºC W 3ºC W -1ºC W -6ºC W -8ºC W Capacity kW 3.01 2.73 2.47 1.76 1.65 1.58 15ºC Input kW. 0.76 0.66 0.60...
Page 16
WINTER OUTDOOR CONDITIONS 12ºC D 7ºC D 4ºC D 0ºC D -4ºC D -7ºC D Indoor Conditions 11ºC W 6ºC W 3ºC W -1ºC W -6ºC W -8ºC W Capacity kW 4446 4264 4132 3838 3335 15ºC Input kW. 1141 1106 1059 1035...
Page 18
7.2 Wiring diagram 7.2.1 Cooling only 7.2.1.1 MSH-07CRN1, MSH-09CRN1 STEP MOTOR INDOOR MOTOR POWER SUPPLY BROWN 1 2 3 4 5 3 2 1 1 2 3 4 5 3 2 1 CN12 BLUE BLACK CN11 COMPRESSOR RELAY C N1 5 C N7 CN16 WAT ER SWITCH...
Page 19
7.2.1.2 MSH-12CRN1 STEP MOTOR INDOOR MOTOR POWER SUPPLY BROWN 1 2 3 4 5 3 2 1 1 2 3 4 5 3 2 1 CN12 BLUE BLACK CN11 COMPRESSOR RELAY C N1 5 C N7 CN16 WAT ER SWITCH TR ANSF ORME R 1 2(N) 3 4 INDOOR UNIT...
Page 20
7.2.2 Heating/cooling 7.2.2.1 MSH-07HRN1, MSH-09HRN1 STEP MOTOR INDOOR MOTOR POWER SUPPLY BROWN 1 2 3 4 5 3 2 1 1 2 3 4 5 3 2 1 CN12 BLUE BLACK CN11 COMPRESSOR RELAY C N1 5 CN13 C N7 CN16 WAT ER SWITCH TR ANSF ORME R...
7.2.2.2 MSH-12HRN1 STEP MOTOR INDOOR MOTOR POWER SUPPLY BROWN 1 2 3 4 5 3 2 1 1 2 3 4 5 3 2 1 CN12 BLUE BLACK CN11 COMPRESSOR RELAY C N1 5 CN13 C N7 CN16 WAT ER SWITCH TR ANSF ORME R 1 2(N) 3 4 INDOOR UNIT...
Page 22
8 Electronic function Electric Control working environment 8.1.1 input voltage: 175~253V 8.1.2 Input power frequency:50Hz 8.1.3 Ambient temperature: -7°C~+43°C 8.1.4 Indoor fan normal working amp is less than 1A, 8.1.5 Outdoor fan. Normal working amp is less than 1.5A 8.1.6 Four-way valve normal working amp is less than 1A.
Page 23
Protection 8.4.1 3 minutes delay at restart for compressor. 8.4.2 Sensor protection at open circuit and breaking disconnection 8.4.3 Fan Speed is out of control. When Indoor Fan Speed is too high(higher than High Fan+300RPM)or too low(lower than 400RPM), the unit stops and LED displays failure information and can’t returns to normal operation automatically.
Page 24
Anti-freezing control to indoor evaporator at cooling mode( T: evaporator temp. ) Condition Compressor Outdoor fan Temp. Time Evaporator T> TE6 Temp. up T< TE6 >5 Minutes Evaporator T> TE5 Temp. down T< TE5 >5 Minutes Dehumidifying mode 8.7.1 The 4-way valve is off in dehumidifying mode 8.7.2 Compressor and Indoor Fan actions in dehumidifying mode Conditions...
Page 25
8.7.3 Low room temperature protection: When room temperature decreases to below 10¡ æ , compressor and outdoor fan will stop(indoor fan is Breeze). Dehumidifying operation will be resumed when room temperature restores to over 13¡ æ . 8.7.4 At dehumidifying mode, the anti-freezing function of the indoor heat exchanger is the same as that of cooling mode.
Page 26
8.8.6 Indoor evaporator high-temperature protection at heating mode Condition Compressor Outdoor fan T= Indoor exchanger temp. Indoor exchanger temp. up T<TE8 TE8<T<TE7 T>TE7 Indoor exchanger temp. down T>TE9 T<TE9 8.8.7. The louver opens to Standard Angle ANGLHEAT when power is on for the first time Defrosting operation (Available for heating only).
Page 27
8.9.4 Defrosting Actions: Defrost 10or 6minutes Compressor 4-way Valve Outdoor Fan Indoor Fan 8.10 Automatic operation mode 8.10.1 The air conditioner automatically selects one of the following operation modes: cooling, heating or fan only according to the temp. difference between room temp. (TA) and set temp. (TS). TA—TS Operation mode TA—TS>2¡...
Page 28
constant and the fan speed is kept at low speed. 8.14.3 Heating: The set temperature decrease 1¡ æ per hour. Two hours later, the set temperature will maintain as a constant and the air circulation is kept at low speed (Cold air proof function takes precedence over all).
9.Troubleshooting 9.1 Display board Infrared Signal Receiver 1: AUTO indicator 2: TIMER indicator 3: PRE.-DEF. Indicator 4: OPERATION indicator 5: SLEEP indicator 9.2 For all heat pump model Failure phenomenon Operation lamp Timer lamp Indoor fan speed has been out of control for over 1 minute ¡...
9.3 Diagnostic Chart 9.3.1 After energizing, no indicator is lighted and the air conditioner can’t be operated. After energizing, the air conditioner can’t be operated Check if AC220V power supply outputs to Indoor PCB. Check if AC220V exists at the primary coil of transformer. Indoor PCB is defective Check if AC14.5V exists at the secondary coil of transformer.
Page 32
9.3.3 Failure phenomenon Failure phenomenon Operation lamp Timer lamp Indoor fan speed has been out of control for over 1 minute ¡ î Indoor room temp. or evaporator sensor is open circuit or short circuit ¡ î Over current protection of the compressor occurs 4 times ¡...
Page 37
3.Dimensions 3.1 Indoor unit 3.2 Outdoor unit...
Page 38
4.Refrigeration cycle diagram “1 drive 3 system” is made up of one “1 drive 1 system” and one “1 drive 2 system”. PMV1 PMV2 Compressor refrigeration distributor 1 drive 2 system SV1 Primary four-way valve SV2 Secondary four-way valve PMV1 PMV2 Electronic expansive valve T1 T2 Indoor pipe temperature sensor condenser four-way valve...
Page 39
5.Operation limits 5.1Cooling operation Outdoor unit air temp. COOLING Indoor air temp. Note : The chart is the result from the continuous operation under constant air temperature conditions. However, excludes the initial pull-down stage. 5.2Heating operation Indoor air temp. Outdoor unit air temp. Note : The chart is the result from the continuous operation under constant air temperature conditions.
Page 40
6.Wiring diagram Indoor unit Outdoor unit...
7.Troubleshooting 7.1 Indoor unit Failure phenomenon Operation lamp Timer lamp Indoor fan speed has been out of control for over 1 minute Indoor room temp. sensor or evaporator temp. sensor is open circuit or short circuit EEROM error Over current protection of the compressor occurs 4 times in 1h r Extinguish Flash at 5Hz 7.2 Outdoor unit (on mainboard)
Page 43
7.4 Failure and Related Causes of Remote Controller Before requesting service or maintenance, please check the following items Changing function can not be set Symptom Checking Item Cause Fan speed can not be Check if “Auto” mode is displayed When “Auto” is chosen, indoor fan will changed choose “Auto”...
Page 44
8 Electronic function Electric Control working environment 8.1.1 input voltage: 175~253V 8.1.2 Input power frequency:50Hz 8.1.3 Ambient temperature: -7°C~+43°C 8.1.4 Indoor fan normal working amp is less than 1A, 8.1.5 Outdoor fan. Normal working amp is less than 1.5A 8.1.6 Four-way valve normal working amp is less than 1A.
Page 45
Protection 8.4.1 The compressor functions protection with a delay of three minutes. 8.4.2 High temp. protection of condenser. 8.4.3 Sensor protection at open circuit and breaking disconnection 8.4.4 Temperature Fuse break protection 8.4.5 Fan Speed is out of control. When Indoor Fan Speed is too high(higher than High Fan+300RPM)or too low(lower than 400RPM), the entire unit stops and LED displays failure information and can’t returns to normal operation automatically.
Page 46
8.7.4 Under dehumidifying mode, the anti-freezing function of the indoor heat exchanger is the same as that of cooling mode. Heating mode 8.8.1 Generally, the 4-way valve is open in heating mode, but it is closed in defrosting mode. 4-way valve must delay 2 minutes compared with compressor if the compressor changed into non-heating mode or turned off.
Page 47
Defrosting operation (Available for heating only). 8.9.1 Defrosting condition: When T3<0 and compressor runs 40 minutes. T3: Temp. of condenser. 8.9.2 Ending condition of defrost If one of following conditions is satisfied, end the defrost and turn into heating: A.The defrost time has reached to 10 minutes. B.T3>20.
Page 48
8.13 Timer Function Requirement The maximum length of timer is 24 hours and the minimum resolving power is 15 minutes. 8.14 Economic Running 8.14.1 The economic running function is available under cooling, heating or auto mode. 8.14.2 Cooling: The set temperature rise 1 per hour.
Page 55
5.Operation limits 5.1Cooling operation Outdoor unit air temp. ¡ æ COOLING Indoor air temp. ¡ æ Note : The chart is the result from the continuous operation under constant air temperature conditions. However, excludes the initial pull-down stage. 5.2Heating operation Indoor air temp.
6.Wiring diagram Indoor unit Outdoor unit T C H S BLACK BLUE CAP3 BLACK BLUE EXPLANATION Y&G CAP2 BLACK BLACK YELLOW LEAVEING COMP B BLACK FACTORY BLACK RAPIDLY BLACK CHECK Y&G Y&G BLACK CHECK ITSELF BLUE BLUE WIRING S.V A DIAGRAM RLUE RLUE...
Page 57
7.Troubleshooting 7.1 Indoor unit Failure phenomenon Operation lamp Timer lamp Indoor fan speed has been out of control for over 1 minute ¡ î Indoor room temp. sensor or evaporator temp. sensor is open circuit ¡ î or short circuit EEPROM error ¡...
Page 58
8 Electronic function Electric Control working environment 8.1.1 input voltage: 175~253V 8.1.2 Input power frequency:50Hz 8.1.3 Ambient temperature: -7°C~+43°C 8.1.4 Indoor fan normal working amp is less than 1A, 8.1.5 Outdoor fan. Normal working amp is less than 1.5A 8.1.6 Four-way valve normal working amp is less than 1A.
Page 59
Protection 8.4.1 The compressor functions protection with a delay of three minutes. 8.4.2 High temp. protection of condenser. 8.4.3 Sensor protection at open circuit and breaking disconnection 8.4.4 Temperature Fuse break protection 8.4.5 Fan Speed is out of control. When Indoor Fan Speed is too high(higher than High Fan+300RPM)or too low(lower than 400RPM), the entire unit stops and LED displays failure information and can’t returns to normal operation automatically.
Page 60
will stop(indoor fan is Breeze). Dehumidifying operation will be resumed when room temperature restores to over 13¡ æ . 8.7.4 Under dehumidifying mode, the anti-freezing function of the indoor heat exchanger is the same as that of cooling mode. Heating mode 8.8.1 Generally, the 4-way valve is open in heating mode, but it is closed in defrosting mode.
Page 61
8.8.6 Indoor evaporator high-temperature protection under heating mode Condition Compressor Outdoor fan Indoor exchanger temp. up TE<TE8 TE8<TE<TE7 TE>TE7 Indoor exchanger temp. down TE>TE9 TE<TE9 Defrosting operation (Available for heating only). 8.9.1 Defrosting condition: When T3<0¡ æ and compressor runs 40 minutes. T3: Temp.
Page 62
8.11 Forced cooling function 8.11.1 Select forced cooling function with the forced cooling button or the switch. 8.11.2 The compressor is unconditionally turned on, after 30 minutes cooling operation whose fan mode is set as low, the A/C operates under the DRY mode with a set temp. of 24¡ æ . 8.11.3 All protections of remote control cooling are available under forced cooling operation.
Page 64
MULTI INVERTER ECO 1. Product features 2. Specification 3. Dimensions 4. Refrigeration cycle diagram 5. Operation limits 6. Capacity table 7. Wiring diagram 8. Electric control functions...
Page 65
1. Product Features Both indoor units can be operated either simultaneously or separately through the utilization of the advanced converter technique and microcomputer control. The flowing volume of refrigerant is adjustable through the electronic expansion valve. High Cooling and Heating capacity is facilitated through the famous-brand frequency converter compressor. Indoor noise is minimized through the optimization of the air flow system design, a four-folded evaporator and a big diameter Cross Flow Fan.
5 Operation Limits Cooling operation Outdoor unit air temp. Indoor air temp. Note :the chart is the result from the continuous operation under constant air temperature conditions. however, excludes the initial pull-down stage. 5.2 Heating operation Indoor air temp. Outdoor unit air temp. Note :the chart is the result from the continuous operation under constant air temperature conditions.
6 Capacity Table 6.1 Capacity table of Inverter Binary Eco type Indoor units can be combined by 7000Btu/h+9000 Btu/h 7000Btu/h+12000 Btu/h 9000Btu/h+9000 Btu/h 9000Btu/h+12000 Btu/h 12000Btu/h+12000 Btu/h Cooling Indoor unit a Indoor unit b 7000Btu/h 2800 9000Btu/h 3000 12000Btu/h 3400 7000Btu/h+7000 Btu/h 2300 2300...
Page 74
Cooling Indoor unit a Indoor unit b Indoor unit c 7000Btu/h 2800 9000Btu/h 3000 12000Btu/h 3400 7000Btu/h+7000 Btu/h 2300 2300 7000Btu/h+9000 Btu/h 2500 2500 7000Btu/h+12000 Btu/h 2200 2800 9000Btu/h+9000 Btu/h 2500 2500 9000Btu/h+12000 Btu/h 2400 3200 12000Btu/h+12000 Btu/h 3200 3200 7000Btu/h*2+9000 Btu/h 2200 2200...
7. Wiring Diagram 7.1 Indoor unit 7/9K 7.2 Indoor unit 12K...
Page 76
Outdoor unit M2OA-18HRIN2 Outdoor unit M3OA-27HRIN2...
Page 77
8. Electric Control Functions 8.1 Control system The control system adopts modular design, that is, all indoor units communicate with outdoor units, ref. to the following figures for the control structure between indoor units and outdoor units. In the structure, the indoor control board receives the information from users (for exam.
Page 78
Volt(V) Volt increase (Resume) MAX=78Hz MAX=70Hz Stop Volt decrease (Limited Frequency) 8.2.2 AC Amp Protection The outdoor control board checks the compressor current and do over-current protection. If the compressor current is over the scheduled value, the system will stop and all indoor units will display malfunction code.
Page 79
8.2.6 Temperature Sensor short/open protection When the outdoor condenser pipe temperature T3, outdoor ambient temperature T4, indoor evaporator outlet are checked out of range 0.05 4.95V, it think temperature sensor short/open temperature protection. The compressor, four-way valve and outdoor fan motor will stop and send malfunction signal to indoor units.
Page 80
Display contents Malfunction or Protection EEPROM Parameter Malfunction No.1 Indoor unit Evaporator outlet temp. sensor malfunction No.2 Indoor unit Evaporator outlet temp. sensor malfunction No.3 Indoor unit Evaporator outlet temp. sensor malfunction Outdoor temp. sensor malfunction Compressor volt protection Obligate Outdoor inverter communication malfunction Top temp.
Page 81
AC INVERTER SERIES II 1. Features 2. Specification 3. Dimensions 4. Refrigeration cycle diagram 5. Operation limits 6. Wiring diagram 7. Troubleshooting 8. Electronic function...
Page 82
1.Features 1.1 Powerful at cooling/heating, 1.3 times and 1.6 times relatively higher than normal same type of models. 1.2 Low voltage start-up function, even at 160 V it can normally start. 1.3 Anti-icing function at cooling mode. 1.4 Anti-cold air function at heating mode. 1.5 Auto-defrosting and heating recovering function at heating mode.
Page 86
3.3 Indoor Unit (MSG-12HRIN2) 3.4 Outdoor Unit...
Page 87
4. Refrigeration Cycle Diagram Indoor unit outdoor unit Valve Sensor of room temp Heat exchanger 4 way valve Sensor Heat exchanger Sensor of temp Sensor of heat exchanger temp Sensor of heat exchanger temp Compressor Valve Capillary...
Page 88
5. Operation Limits 5.1 Cooling operation Outdoor unit air temp. Indoor air temp. Note :the chart is the result from the continuous operation under constant air temperature conditions. however, excludes the initial pull-down stage. 5.2 Heating operation Indoor air temp. Outdoor unit air temp.
Page 89
Wiring Diagram Indoor unit MSG-09HRI MSG-07HRIN2 MSG-09HRIN2 Indoor unit MSG-12HRI BLACK YELLOW WHITE RED BLACK YELLOW...
Page 92
7.Troubleshooting 7.1 Indoor Unit Error Display Function LED4 operation LED2 defrosting LED1 timer LED4 auto LED2 LED1 LED3 LED4 LED STATUS defrost Timer Auto operation Mold protection Compressor top protection against temperature Open or short circuit of outdoor temperature sensor Over load or too low voltage protection Room temperature or evaporator temperature sensor open or short circuit of...
Page 93
8 .Electronic Function General Protection 8.1.1 Temperature Protection of Compressor Top 8.1.2 3 minutes Delayed Starting Protection of the Compressor 8.1.3 Voltage Protection 8.1.4 The frequency Up-Down speed at which the compressor starts, operates and shuts off will be subject to the following principles (outdoor chip): 1HZ/S 92Hz 2HZ/S...
Page 94
8.2.5 Performance at Auto mode at Fan-only status is the same as that at Auto mode at cooling status, provided that the set temperature is 24°c. °C 27.5 High 27.0 25.5 25.0 Cooling Mode Function Requirement 8.3.1 At cooling mode the 4 way valve is off. 8.3.2 Anti-icing Control for Indoor Evaporator When the temperature of indoor heat exchanger drops to...
Page 95
8.3.4 Indoor fan operates in accordance with the following principles: 8.3.4.1 When indoor fan is in operation, it can be remote controlled to High/Mid/Low/Auto modes. 8.3.4.2 The fan speed at Auto mode in cooling status is subject to the following: °C room temperature - set temperature +4.0...
Page 96
8.4.6 At dehumidifying mode, the power voltage and outdoor temperature limitation to the highest frequency when compressor starts and operates is the same as that at cooling mode. Heating Mode Function Requirement 8.5.1 At heating mode, the 4 way valve is on, during defrosting operation, it is off. 8.5.2 Outdoor fan usually turns on or off in accordance with the action of compressor, except for defrosting and ending of the defrost.
Page 97
8.5.5 Outdoor Unit current control when heating Note: The frequency in the table Compressor off goes down in accordance (11.5A) 10.0A with the present frequency, frequency down determine every 2 seconds whether it keeps going (10.5A) 8.8A down or it is recovering. frequency unchanged (9.2A) 7.4A 8.5.6...
Page 98
The temperature of outdoor heat exchanger remains consecutively lower than 3°c for more than 80 minutes, and the temperature remains consecutively Ti2 for more than 3 minutes. Model Ti2: MSG-09HRI : -2°c MSG-12HRI : -4°c MSG-09HRIN2 : -7°c MSG-09HRIN2 : -7°c The temperature of outdoor heat exchanger remains consecutively lower than 3°c for more than 120 minutes, and the temperature remains consecutively Ti3 for more than 3 minutes.
Page 99
8.5.9 Set Function Test When it is detected that the outdoor temperature is between 5 - 9°c and room temperature is between 18 - 22°c, provided that the heating operation remains consecutively more than 30 minutes, the compressor's highest operational frequency is FMAX=F8=96HZ. If any of the above conditions is not met, it will quit from set frequency operation.
4.Refrigeration cycle diagram 4.1 Cooling/heating Indoor unit outdoor unit Valve Sensor of room temp 4 way valve Heat exchanger Heat exchanger Sensor of heat exchanger temp Compressor Valve Capillary 4.2 Cooling only Indoor unit outdoor unit Valve Sensor of room temp Heat exchanger Heat exchanger Sensor of heat exchanger temp...
Page 107
5.Operation limits 5.1Cooling operation Outdoor unit air temp. ¡ æ COOLING Indoor air temp. ¡ æ Note : The chart is the result from the continuous operation under constant air temperature conditions. However, excludes the initial pull-down stage. 5.2Heating operation Indoor air temp.
Page 108
6.Wiring diagram 6.1 Cooling only 6.1.1 MSG1-07CRN2, MSG1-09CRN2 POWER SUPPLY INDOOR UNIT 1 2( N ) Y£ ¦ G COMPRESSOR MOTOR Y£ ¦ G Y£ ¦ G B L U COMPRESSOR CAPACITOR CAPACITOR...
Page 109
6.1.2 MSG1-12CRN2 INDOOR UNIT 1 2 ( OUTDOOR UNIT Y£ ¦ G COMPRESSOR MOTOR Y£ ¦ G Y£ ¦ G COMPRESSOR CAPACITOR CAPACITOR...
Page 112
7.Troubleshooting 7.1 For all cooling only model Failure phenomenon Operation lamp Timer lamp Indoor fan speed has been out of control for over 1 minute ¡ î Indoor room temp. or evaporator sensor is open circuit or short ¡ î circuit Over current protection of the compressor occurs 4 times ¡...
Page 113
TE2: Anti-cold wind, from Breeze to Setting Fan Speed temperature TE3: Anti-cold wind, from Setting Fan Speed to Breeze temperature TE4: Anti-cold wind, from Breeze to Fan Off temperature TE5: Evaporator low temperature protection entering temperature TE6: Evaporator low temperature protection restoring temperature TE7: Evaporator high temperature protection, compressor off temperature TE8: Evaporator high temperature protection, fan off temperature TE9: Evaporator high temperature protection, restoring temperature...
Page 114
operation automatically. Fan-only mode Fan speed is high/mid/low/ Auto Cooling mode The 4-way valve is closed at cooling mode. The action of the compressor and the outdoor fan: Condition Compressor Outdoor fan Temp. up T> Ts+1 T<Ts+1 Temp. down T> Ts T<Ts Auto fan at cooling mode: Condition...
Page 115
8.7.3 Low room temperature protection: When room temperature decreases to below 10¡ æ , compressor and outdoor fan will stop(indoor fan is Breeze). Dehumidifying operation will be resumed when room temperature restores to over 13¡ æ . 8.7.4 At dehumidifying mode, the anti-freezing function of the indoor heat exchanger is the same as that of cooling mode.
Page 116
8.8.6 Indoor evaporator high-temperature protection at heating mode Condition Compressor Outdoor fan T= Indoor exchanger temp. Indoor exchanger temp. up T<TE8 TE8<T<TE7 T>TE7 Indoor exchanger temp. down T>TE9 T<TE9 Defrosting operation (Available for heating only). 8.9.1 Defrosting condition: Defrosting starts when either of the following ¢ Ù &¢ Ú : ¢...
Page 117
8.9.4 Defrosting Actions: Defrost 10or 6minutes Compressor 4-way Valve Outdoor Fan Indoor Fan 8.9.7 Turn into heating mode, turn off the heating mode in 7 minutes. 8.10 Automatic operation mode 8.10.1 The air conditioner automatically selects one of the following operation modes: cooling, heating or fan only according to the temp.
Page 118
8.14.3 Heating: The set temperature decrease 1¡ æ per hour. Two hours later, the set temperature will maintain as a constant and the air circulation is kept at low speed (Cold air proof function takes precedence over all). 8.14.4 Auto: The economic running function operates in accordance with selected running mode by auto mode.
Page 126
3.Dimensions 3.1 Indoor unit 3.2 Outdoor unit...
Page 127
4.Refrigeration cycle diagram 4.1 Cooling/heating Indoor unit outdoor unit Valve Sensor of room temp 4 way valve Heat exchanger Heat exchanger Sensor of heat exchanger temp Compressor Valve Capillary 4.2 Cooling only Indoor unit outdoor unit Valve Sensor of room temp Heat exchanger Heat exchanger Sensor of heat exchanger temp...
Page 128
5.Operation limits 5.1Cooling operation Outdoor unit air temp. ¡ æ COOLING Indoor air temp. ¡ æ Note : The chart is the result from the continuous operation under constant air temperature conditions. However, excludes the initial pull-down stage. 5.2Heating operation Indoor air temp.
Page 129
6.Wiring diagram 6.1 Cooling only POWER SUPPLY INDOOR UNIT 1 2 ( N) Y£ ¦ G R ED COMPRESSOR MOTOR Y£ ¦ G Y£ ¦ G B L U B L U COMPRESSOR CAPACITOR CAPACITOR...
Page 131
7.Troubleshooting 7.1 For all cooling only model Failure phenomenon Operation lamp Timer lamp Indoor fan speed has been out of control for over 1 minute ¡ î Indoor room temp. or evaporator sensor is open circuit or short circuit ¡ î Over current protection of the compressor occurs 4 times ¡...
Page 132
8 Electronic function Electric Control working environment 8.1.1 Input voltage: 175~253V 8.1.2 Input power frequency:50Hz 8.1.3 Ambient temperature: -7°C~+43°C 8.1.4 Indoor fan normal working amp is less than 1A, 8.1.5 Outdoor fan. Normal working amp is less than 1.5A 8.1.6 Four-way valve normal working amp is less than 1A.
Page 133
Anti cold air at heating mode Anti frozen at heating mode Protection 8.1.1 The compressor functions protection with a delay of three minutes. 8.1.2 Sensor protection at open circuit and breaking disconnection 8.1.3 Temperature Fuse break protection 8.1.4 Fan Speed is out of control. When Indoor Fan Speed is too high(higher than High Fan+300RPM)or too low(lower than 400RPM), the entire unit stops and LED displays failure information and can’t returns to normal operation automatically.
Page 134
Auto fan: Condition Indoor fan speed T=Indoor Temp.-Setting Temp. Temp. up T<3¡ æ 3¡ æ <T<5¡ æ Med. T>5¡ æ High Temp. down T> 3¡ æ High 1¡ æ <T<3¡ æ Med. T<1¡ æ Anti-freezing control to indoor evaporator ( T: evaporator temp. ) Condition Compressor Outdoor fan...
Page 135
minutes after starting and then judge temperature. Meanwhile other protections are still valid. Condition Compressor Outdoor fan Room temp. up T> Ts+3 T<Ts+3 Room temp. down T< Ts+2 T>Ts+2 8.8.4 Indoor Fan actions at heating mode 8.8.4.1 Indoor Fan can be set at HIGH/MID/LOW/AUTO by using a remote controller, but Anti-cold wind function prevails.
Page 136
A: The compressor keeps running for 40 minutes or more. B: The temperature difference of evaporator temp and room temperature meets one of the following: Temp. of evaporator---room temp. ¡ æ Fan speed is high ¡ Ü TH DEFROST Fan speed is mid ¡...
Page 137
8.10.1 The air conditioner automatically selects one of the following operation modes: cooling, heating or fan only according to the temp. difference between room temp. (TA) and set temp. (TS). TA¡ ª TS Operation mode TA¡ ª TS>2¡ æ Cooling -1¡...
Page 139
LIGHT STAR SERIES 1. Features 2. Specification 3. Dimensions 4. Refrigeration cycle diagram 5. Operation limits 6. Wiring diagram 7. Troubleshooting...
Page 140
1. Features Compact design Flexible wiring connection There is a separate terminal in indoor unit, so it is very easy and flexible to connect the indoor unit and outdoor unit. ABS outdoor unit. Optional panels available...
Page 146
4.Refrigeration cycle diagram 4.1 Cooling/heating Indoor unit outdoor unit Valve Sensor of room temp 4 way valve Heat exchanger Heat exchanger Sensor of heat exchanger temp Compressor Valve Capillary 4.2 Cooling only Indoor unit outdoor unit Valve Sensor of room temp Heat exchanger Heat exchanger Sensor of heat exchanger temp...
Page 147
5.Operation limits 5.1Cooling operation(less than 18000Btu/h) Outdoor unit air temp. ¡ æ COOLING Indoor air temp. ¡ æ Note : The chart is the result from the continuous operation under constant air temperature conditions. However, excludes the initial pull-down stage. 5.2Heating operation(less than 18000Btu/h) Indoor air temp.
Page 148
6.Wiring diagram 6.1 Diagram for cooling only 7000-9000Btu/h indoor unit 12000Btu/h indoor unit 7000-12000Btu/h outdoor unit INDOOR UNIT 1 2 ( N) Y£ ¦ G R ED COMPRESSOR MOTOR Y£ ¦ G Y£ ¦ G B L U B L U COMPRESSOR CAPACITOR CAPACITOR...
Page 149
6.2Heating/cooling 7000-9000Btu/h Indoor unit 12000Btu/h indoor unit 7000Btu/h-12000Btu/h outdoor unit...
7.Troubleshooting 7.1 For all cooling only model Failure phenomenon Operation lamp Timer lamp Indoor fan speed has been out of control for over 1 minute ¡ î Indoor room temp. or evaporator sensor is open circuit or short circuit ¡ î Over current protection of the compressor occurs 4 times ¡...
Page 151
Glory Giant 2 1. Features 1.1 The evaporator employs a Multi-bend structure which enlarges the heat exchange surface. 1.2 The front panel is tightly fixed with the front frame by simply buckling the latter with a buckle mechanism on the panel. 1.3 The manual force switch employs comfortable switch push buttons.
Page 153
3. Dimensions 3.2 Outdoor unit 142.9 589.6...
Page 154
4. Refrigeration cycle diagram 4.1 Heating and cooling Indoor unit outdoor unit Valve Sensor of room temp 4 way valve Heat exchanger Heat exchanger Sensor of heat Sensor of heat exchanger temp exchanger temp Compressor Valve Capillary Reservoir 4.2 Cooling only Indoor unit outdoor unit Valve...
Page 155
5. Operation limits 5.1 Cooling operation Outdoor unit air temp. Indoor air temp. Note :The chart is the result from the continuous operation under constant air temperature conditions. However, excludes the initial pull-down stage. 5.2 Heating operation Indoor air temp. Outdoor unit air temp.
Page 156
6. Wiring diagram 6.1 Cooling Only MSG-36CR 220-240V~,50Hz and 380V~,50Hz MSG-36CR 220-240V~,50Hz MSG-36CR 380V~,50Hz...
Page 157
6.2 Heat pump MSG-36HR 220-240V~,50Hz and 380V~,50Hz MSG-36HR 220-240V~,50Hz and 380V~,50Hz MSG-36HR 380V~,50Hz...
Page 158
Troubleshooting 7.1 Indoor unit LED status Operation indicator, time indicator, Defrosting (fan Four times Current protection (PRCUR1) 5Hz indicator, for cooling only type)indicator flicker at 5Hz Time indicator flickers at 5Hz the room temperature sensor o is open or short Operation indicator flickers at 5Hz the evaporator temperature sensor is open or short Defrosting indicator flickers at 5Hz...
Page 159
8. Electronic Control Principle of Large Cooling Capacity Split Model A/C Fan only mode Fan speed is high/mid/low/ Auto Cooling mode The 4-way valve is closed at cooling mode. The action of the compressor and the outdoor fan: T: Room temp. Ts: Setting temp.
Page 160
8.4.4 Indoor Fan actions at heating mode Indoor Fan can be set at HIGH/MID/LOW/AUTO by using a remote controller, but Anti-cold wind function prevails. Condition Indoor fan speed T= Indoor exchanger temp. Indoor exchanger temp. up T<TE1 TE1<T<TE2 Low speed T>TE2 Setting fan speed Indoor exchanger temp.
Page 161
8.5.3 Time sequence of the whole defrosting procedure is as follows: Defrost 10or 6minutes Compressor 4-way Valve Outdoor Fan Indoor Fan Auto mode 8.6.1 When running in automatic mode, the air conditioner automatically selects one of the following operation modes: cooling, heating or ventilation according to the difference between room temp. (TA) and set temp.
Page 162
8.8.2. Forced Auto 8.8.2.1 Remote control signal can be received in forced auto mode. When receiving the signals, the forced auto mode will be canceled and the A/C changes to remote control status and performs operation as the signals indicates. 8.8.2.2 The system performs control according to the remote control auto mode with a set temperature of 24°c.
Page 163
Glory Giant 1 1. Features 1.1 The evaporator employs a Multi-bend structure which enlarges the heat exchange surface. 1.2 The front panel is tightly fixed with the front frame by simply buckling the latter with a buckle mechanism on the panel. 1.3 The manual force switch employs comfortable switch push buttons.
Page 167
Model MSG-30CRN2 MSG-30HRN2 Power supply Ph-V-Hz 3Ph,380-420V,50Hz 3Ph,380-420V,50Hz Cooling Capacity Btu/h 28000 28000 Input 3300 3300 Rated current Btu/w.h 8.5, Heating Capacity Btu/h 33000 Input 3300 Rated current Moisture Removal Max. input consumption 3800 3800 Max. Current Starting current Compressor Model HQ034YAA HQ034YAA...
Page 168
3. Dimensions 3.1 Indoor unit 3.2 Outdoor unit...
Page 169
4. Refrigeration cycle diagram 4.1 Heating and cooling Indoor unit outdoor unit Valve Sensor of room temp 4 way valve Heat exchanger Heat exchanger Sensor of heat Sensor of heat exchanger temp exchanger temp Compressor Valve Capillary Reservoir 4.2 Cooling only Indoor unit outdoor unit Valve...
Page 170
5. Operation limits 5.1 Cooling operation Outdoor unit air temp. ¡ æ Indoor air temp. ¡ æ Note :The chart is the result from the continuous operation under constant air temperature conditions. However, excludes the initial pull-down stage. 5.2 Heating operation Indoor air temp.
Page 175
Troubleshooting LED status Operation indicator, time indicator, Defrosting indicator Four times Current protection (PRCUR1) 5Hz (fan indicator, for cooling only type)auto indicator flicker at 5Hz Time indicator flickers at 5Hz the room temperature sensor o is open or short Operation indicator flickers at 5Hz the evaporator temperature sensor is open or short Defrosting indicator flickers at 5Hz the condenser temperature sensor is open or short...
Page 176
8. Electronic Control Principle of Large Cooling Capacity Split Model A/C Fan only mode Fan speed is high/mid/low/ Auto Cooling mode The 4-way valve is closed at cooling mode. The action of the compressor and the outdoor fan: T: Room temp. Ts: Setting temp.
Page 177
8.4.4 Indoor Fan actions at heating mode Indoor Fan can be set at HIGH/MID/LOW/AUTO by using a remote controller, Anti-cold wind function 1. Condition Indoor fan speed T= Indoor exchanger temp. Indoor exchanger temp. up T<TE1 TE1<T<TE2 Low speed T>TE2 Setting fan speed Indoor exchanger temp.
Page 178
8.5.3 Time sequence of the whole defrosting procedure is as follows: Defrost 10or 6minutes Compressor 4-way Valve Outdoor Fan Indoor Fan Remark: when the evaporator pipe sensor temp. more than TE16, The indoor fan start to run. Auto mode 8.6.1 When running in automatic mode, the air conditioner automatically selects one of the following operation modes: cooling, heating or ventilation according to the difference between room temp.
Page 179
off, the buzzer buzzes lasts for 1 seconds, then A/C turns to be closedown status. 8.8.2. Forced Auto 8.8.2.1 Remote control signal can be received in forced auto mode. When receiving the signals, the forced auto mode will be canceled and the A/C changes to remote control status and performs operation as the signals indicates.
Page 193
4.Refrigeration cycle diagram 4.1 Cooling/heating Indoor unit outdoor unit Valve Sensor of room temp 4 way valve Heat exchanger Heat exchanger Sensor of heat exchanger temp Compressor Valve Capillary 4.2 Cooling only Indoor unit outdoor unit Valve Sensor of room temp Heat exchanger Heat exchanger Sensor of heat exchanger temp...
Page 194
5.Operation limits 5.1Cooling operation Outdoor unit air temp. ¡ æ COOLING Indoor air temp. ¡ æ Note : The chart is the result from the continuous operation under constant air temperature conditions. However, excludes the initial pull-down stage. 5.2Heating operation Indoor air temp.
Page 195
6.Wiring diagram 6.1 Cooling only 6.1.1 MSG-05CR Indoor unit POWER SUPPLY INDOOR UNIT 1 2( N ) Y£ ¦ G COMPRESSOR MOTOR Y£ ¦ G Y£ ¦ G B L U COMPRESSOR CAPACITOR CAPACITOR...
Page 196
6.1.2 MSG-07CR,MSG-07CRN2, MSG-09CR,MSG-09CRN2 POWER SUPPLY INDOOR UNIT 1 2 ( OUTDOOR UNIT Y£ ¦ G COMPRESSOR MOTOR Y£ ¦ G Y£ ¦ G COMPRESSOR CAPACITOR CAPACITOR...
Page 197
6.1.3 MSG-12CR Indoor unit (A Type) POWER SUPPLY INDOOR UNIT 1 2 ( OUTDOOR UNIT Y£ ¦ G COMPRESSOR MOTOR Y£ ¦ G Y£ ¦ G COMPRESSOR CAPACITOR CAPACITOR...
Page 198
6.1.4 MSG-12CR (B Type), MSG-12CR N2 INDOOR UNIT 1 2 ( OUTDOOR UNIT Y£ ¦ G COMPRESSOR MOTOR Y£ ¦ G Y£ ¦ G COMPRESSOR CAPACITOR CAPACITOR...
Page 199
6.1.5 MSG-18CR ,MSG-21CR, MSG-18CRN2 ,MSG-21CRN2 COMPRESSOR RELAY TRANSFORMER BLUE WHITE BROWN SWITCH BOARD CN14 CURRENT DETECTOR CN10 INDOOR MOTOR INDOOR UNIT 1 2 ( OUTDOOR UNIT Y£ ¦ G COMPRESSOR MOTOR Y£ ¦ G Y£ ¦ G COMPRESSOR CAPACITOR CAPACITOR...
Page 202
6.2.3 MSG-18HR,MSG-21HR,,MSG-18HRN2,MSG-21HRN2 COMPRESSOR RELAY TRANSFORMER BLUE WHITE BROWN SWITCH BOARD CN14 CURRENT DETECTOR CN10 INDOOR MOTOR...
Page 203
7.Troubleshooting 7.1 For all cooling only model Failure phenomenon Operation lamp Timer lamp Indoor fan speed has been out of control for over 1 minute ¡ î Indoor room temp. or evaporator sensor is open circuit or short ¡ î circuit Over current protection of the compressor occurs 4 times ¡...
Page 204
TE2: Anti-cold wind, from Breeze to Setting Fan Speed temperature TE3: Anti-cold wind, from Setting Fan Speed to Breeze temperature TE4: Anti-cold wind, from Breeze to Fan Off temperature TE5: Evaporator low temperature protection entering temperature TE6: Evaporator low temperature protection restoring temperature TE7: Evaporator high temperature protection, compressor off temperature TE8: Evaporator high temperature protection, fan off temperature TE9: Evaporator high temperature protection, restoring temperature...
Page 205
Fan-only mode Fan speed is high/mid/low/ Auto Cooling mode The 4-way valve is closed at cooling mode. The action of the compressor and the outdoor fan: Condition Compressor Outdoor fan Temp. up T> Ts+1 T<Ts+1 Temp. down T> Ts T<Ts Auto fan at cooling mode: Condition Indoor fan speed...
Page 206
8.7.3 Low room temperature protection: When room temperature decreases to below 10¡ æ , compressor and outdoor fan will stop(indoor fan is Breeze). Dehumidifying operation will be resumed when room temperature restores to over 13¡ æ . 8.7.4 At dehumidifying mode, the anti-freezing function of the indoor heat exchanger is the same as that of cooling mode.
Page 207
8.8.6 Indoor evaporator high-temperature protection at heating mode Condition Compressor Outdoor fan T= Indoor exchanger temp. Indoor exchanger temp. up T<TE8 TE8<T<TE7 T>TE7 Indoor exchanger temp. down T>TE9 T<TE9 Defrosting operation (Available for heating only). 8.9.1 Defrosting condition: Defrosting starts when either of the following ¢ Ù &¢ Ú : ¢...
Page 208
8.9.4 Defrosting Actions: Defrost 10or 6minutes Compressor 4-way Valve Outdoor Fan Indoor Fan 8.9.7 Turn into heating mode, turn off the heating mode in 7 minutes. 8.10 Automatic operation mode 8.10.1 The air conditioner automatically selects one of the following operation modes: cooling, heating or fan only according to the temp.
Page 209
The set temperature decrease 1¡ æ per hour. Two hours later, the set temperature will maintain as a constant and the air circulation is kept at low speed (Cold air proof function takes precedence over all). 8.14.4 Auto: The economic running function operates in accordance with selected running mode by auto mode. 8.15 Auto restart function In case of a sudden power failure, this function automatically sets the unit to previous settings before...
BRIGHT ECO SERIES 1. Features 2. Specification 3. Dimensions 4. Refrigeration cycle diagram 5. Operation limits 6. Wiring diagram 7. Troubleshooting 8. Electric control functions...
Page 214
Features Compact design Flexible wiring connection There is a separate terminal in indoor unit, so it is very easy and flexible to connect the indoor unit and outdoor unit. Ultra strong rust proof performance, with special cataphoric treatment. Optional panels available...
Page 220
3.1.4 Indoor unit(24000-30000Btu/h) 3.2 Outdoor unit 3.2.1 Outdoor unit (7000-9000Btu/h) 3.2.2 Outdoor unit (12000Btu/h)
Page 221
3.2.3 Outdoor unit (18000Btu/h) 3.2.4 Outdoor unit (21000-30000Btu/h)
Page 222
4. Refrigeration cycle diagram 4.1Heating/cooling Indoor unit outdoor unit Valve Sensor of room temp 4 way valve Heat exchanger Heat exchanger Sensor of heat exchanger temp Compressor Valve Capillary drier filter 4.2 Cooling only Indoor unit outdoor unit Valve Sensor of room temp Heat exchanger Heat exchanger Sensor of heat exchanger temp...
Page 223
5. Operation limits 5.1 Cooling operation Outdoor unit air temp. ¡ æ COOLING Indoor air temp. ¡ æ Note : The chart is the result from the continuous operation under constant air temperature conditions. However, excludes the initial pull-down stage. 5.2 Heating operation Indoor air temp.
Page 224
6.Wiring diagram 6.1.1 MSB-07CRN2, MSB-09CRN2 I N D O O R U N I T 1 2 ( N) O U T D O O R U N I T Y £ ¦ BL ACK B L A C K OVERL OAD REL AY R E D...
Page 225
6.1.3 MSB-18CRN2£ ¬ MSB-21CRN2 6.1.4 MSG-24CRN2,MSG-30CRN2 DI SPLAY BOARD AN CA SWING Y&G MOTOR INDOOR CN10 MAIN BOARD Y&G Y&G PIPE TEMPERATURE SENSOR CN11 DOOR POWER ROOM TEMPERATURE SENSOR ORMER...
Page 232
7.Troubleshooting 7.1 7000Btu/h-12000Btu/h 7.1.1 For all cooling only model Failure phenomenon Operation lamp Timer lamp Indoor fan speed has been out of control for over 1 minute ¡ î Indoor room temp. or evaporator sensor is open circuit or short circuit ¡...
Page 233
BRIGHT STAR SERIES (Capacity more than 18000Btu/h) 1. Features 1.1 The evaporator employs a 2-bend structure which enlarges the heat exchange surface. 1.2 With three grilles, the outlet frame and the base plate are integrally designed and of easy installation. 1.3 The front panel is tightly fixed with the front frame by simply buckling the latter with a buckle mechanism on the panel.
Page 237
3.3 Outdoor unit (18000) 3.4 Indoor unit(21000-30000Btu/h)
Page 238
4. Refrigeration cycle diagram 4.1 Heating and cooling Indoor unit outdoor unit Valve Sensor of room temp 4 way valve Heat exchanger Heat exchanger Sensor of heat Sensor of heat exchanger temp exchanger temp Compressor Valve Capillary Reservoir 4.2 Cooling only Indoor unit outdoor unit Valve...
Page 239
5. Operation limits 5.1 Cooling operation Outdoor unit air temp. ¡ æ Indoor air temp. ¡ æ Note :The chart is the result from the continuous operation under constant air temperature conditions. However, excludes the initial pull-down stage. 5.2 Heating operation Indoor air temp.
Troubleshooting LED status Operation indicator, time indicator, Defrosting (fan Four times Current protection (PRCUR1) 5Hz indicator, for cooling only type)indicator flicker at 5Hz Time indicator flickers at 5Hz the room temperature sensor o is open or short Operation indicator flickers at 5Hz the evaporator temperature sensor is open or short Defrosting indicator flickers at 5Hz the condenser temperature sensor is open or short...
Page 246
8.3 Dehumidifying mode 8.3.1 Indoor fan speed at low speed. 8.3.2 Protection is same as cooling mode. Heating mode 8.4.1 Generally, the 4-way valve is open in heating mode, but it is closed in defrosting mode. 4-way valve must delay 2 minutes compared with compressor if the compressor changed into non-heating mode or turned off.
Page 247
Defrosting mode 8.5.1 Conditions of defrost: Defrosting starts when either of the following : T3 lower than 0°c, lasts for more than 40 minutes, provided that the time period when the temperature is lower than -3°c consecutively reaches 3 minutes. Calculate from the end of latest defrost, evaporator high temp.
Page 248
8.8.1 Forced Cooling 8.8.1.1 In forced cooling mode, the remote signal is not accepted. 8.8.1.2 When entering the forced cooling mode, the operating light is turned on. The buzzer buzzes twice, each lasts 0.5 second with 0.5 second interval. 8.8.1.3 The compressor is unconditionally turned on, after 30 minutes cooling operation whose fan mode is set as low, the A/C operates in the forced auto mode under the requirements of the forced auto mode.
Page 250
BRIGHT STAR SERIES(Capacity less than 18000Btu/h) Features Specification Dimensions Refrigeration cycle diagram Operation limits Wiring diagram Troubleshooting Electric control functions BRIGHT STAR SERIES(Capacity more than 18000Btu/h) Features Specification Dimensions Refrigeration cycle diagram Operation limits Wiring diagram Troubleshooting Electric control functions...
Page 251
1. Features 1.1 Compact design 1.2 Flexible wiring connection There is a separate terminal in indoor unit, so it is very easy and flexible to connect the indoor unit and outdoor unit. 1.3 Ultra strong rust proof performance, with special cataphoric treatment. 1.4 Optional panels available...
Page 253
Model MSB-09HR MSB-12CR MSB-12HR Power supply Ph-V-Hz 220-240V,50HZ 220-240V,50HZ 220-240V,50HZ Capacity Btu/h 9000 12000 12000 Input 1250 1300 Cooling Rated current Btu/w.h Capacity Btu/h 9500 13000 Input 1300 Heating Rated current Moisture Removal Max. input consumption 1250 1300 1400 Starting current Model PH170X1C-4DZ2 PH200X2C-4FT...
Page 254
3.Dimensions 3.1 Indoor unit 5000-9000Btu/h 12000Btu/h...
Page 255
3.2 Outdoor unit (5000-9000Btu/h) 3.3 Outdoor unit (12000Btu/h)
Page 256
4.Refrigeration cycle diagram 4.1 Cooling/heating Indoor unit outdoor unit Valve Sensor of room temp 4 way valve Heat exchanger Heat exchanger Sensor of heat exchanger temp Compressor Valve Capillary 4.2 Cooling only Indoor unit outdoor unit Valve Sensor of room temp Heat exchanger Heat exchanger Sensor of heat exchanger temp...
Page 257
5.Operation limits 5.1Cooling operation(Less than 18000Btu/h) Outdoor unit air temp. COOLING Indoor air temp. Note : The chart is the result from the continuous operation under constant air temperature conditions. However, excludes the initial pull-down stage. 5.2 Heating operation Indoor air temp. Outdoor unit air temp.
Page 258
6.Wiring diagram 6.1 Cooling only 5000-9000Btu/h 12000Btu/h...
Page 262
7.Troubleshooting(Capacity less than 18000Btu/h) 7.1 For all cooling only model Failure phenomenon Operation lamp Timer lamp Indoor fan speed has been out of control for over 1 minute Indoor room temp. or evaporator sensor is open circuit or short circuit Over current protection of the compressor occurs 4 times EEPROM error No over-zero signal...
Page 263
: High wind, defrosting temperature difference DEFROST : Middle wind, defrosting temperature difference DEFROST : Low wind, defrosting temperature difference DEFROST TE1: Anti-cold wind, from Fan Off to Breeze temperature TE2: Anti-cold wind, from Breeze to Setting Fan Speed temperature TE3: Anti-cold wind, from Setting Fan Speed to Breeze temperature TE4: Anti-cold wind, from Breeze to Fan Off temperature TE5: Evaporator low temperature protection entering temperature...
8.4.7 Condition Indoor fan Compressor Outdoor fan Remark Current up I< I RESTORE <I< I Heating mode RESTORE Low speed Cooling mode <I<I After 5 Minutes 5MIN <I< I After 3 Seconds 5MIN 3SEC Current <I< I After 3 Seconds 5MIN 3SEC down...
Page 265
Dehumidifying mode 8.7.1 The 4-way valve is off at dehumidifying mode 8.7.2 Compressor and Indoor Fan actions in dehumidifying mode Conditions Indoor Fan Compressor and Outdoor Fan ON 6 minutes TA ≥ TS+2 BREEZE OFF 4minutes ON 5minutes TS ≤TA TS+2 BREEZE OFF 5minutes ON 4minutes...
Page 266
Condition Indoor fan speed T= Indoor exchanger temp. Indoor exchanger temp. up T<TE1 TE1<T<TE2 Breeze T>TE2 Setting fan speed Indoor exchanger temp. down T> TE3 Setting fan speed TE3<T<TE4 Breeze T<TE4 Auto wind Condition Indoor fan speed T=Indoor Temp.-Setting Temp. Room temp.
Page 267
8.9.2 Defrosting time If the temp. difference condition is satisfied for less than 40 minutes, this can be regarded as severe frosting. The defrosting time is 10 minutes. If the temp. difference condition is satisfied for more than 40 minutes, the defrosting time is 6 minutes.
Page 268
8.10 Automatic operation mode When running in automatic mode, the air conditioner automatically selects one of the following operation modes: cooling, heating or fan only according to the temp. difference between room temp. (TA) and set temp. (TS). TA TS Operation mode TA TS>2 Cooling...
Page 270
The service rules of the R410A product 1. The service rules of the new refrigerant R407C product Midea uses the green refrigerant R407C firstly in China. Its thermal characters are similar to R22, but there is little difference between them.
Page 271
about 30 minutes, and vacuity is less than 133Pa. 1.3 Precautions: 1.3.1 Regulations Being liquefied vapor, R-407C and R-410A are high-pressure vapor, the high-pressure gas regulation is applicable. Before use it, please refer to high-pressure gas regulation. To prevent the high-pressure vapor from causing damage, the regulation should be followed.
Page 272
chain reaction proceeds continually, the water in the system will be more and more. It will cause the capillary ice blocking; at the same time, acidity of working substance circulated in the system will be higher and higher (the value of PH is lower and lower), and it may corrode the components and parts in the system.
Diagnostic Chart(5000Btu/h-12000Btu/h) 1. Self-diagnose the failure Midea units have self-diagnose function. Note: for the following series BRIGHT STAR SERIES,BRIGHT ECO SERIES; GLORY STAR SERIES,GLORY ECO SERIES; LIGHT STAR SERIES. 2. After energizing, no indicator is lighted and the air conditioner can’t be operated.
Page 274
4. Failure phenomenon for cooling only type Failure phenomenon Operation lamp Timer lamp Indoor fan speed has been out of control for over 1 minute Indoor room temp. or evaporator sensor is open circuit or short circuit Over current protection of the compressor occurs 4 times EEPROM error r Extinguish Flash at 5Hz...
Page 275
5. Failure phenomenon(heat pump) Failure phenomenon Operation lamp Timer lamp Defrosting lamp Over current protection of the compressor occurs 4 times Indoor fan speed has been out of control for over 1 minute No over-zero signal Temp. sensor on indoor evaporator is open circuit or short circuit Indoor room temp.
Page 276
Operation lamp flashes and Timer lamp off. Change the main control board 5.4 Operation lamp off ,Timer lamp off and Defrosting lamp flashes. Is connection to connector good? Repair connector Replace the sensor 5.5 Operation lamp off, Timer lamp flashes and Defrosting lamp off Is connection to connector good? Replace the sensor Repair connector...
Page 278
1.Features 1.1 Powerful at cooling/heating. 1.2 Low voltage start-up function. 1.3 Anti-icing function at cooling mode. 1.4 Anti-cold air function at heating mode. 1.5 Auto-defrosting. 1.6 Outdoor electric current protection 1.7 Temperature protection of the outdoor compressor top. 1.8 Restart protection for the compressor. 1.9 Error self -diagnosis function.
8 PCB diagram 8.1 Display board 9012 LED1 LED2 LED3 DISP2 74HC164 8LED DEF R DATA TIME Y FROM INDOOR PCB DIGI AUTO G REMOTE 47u/16V 9012 R1 102 9013 R4 221 REC1 dig.1 DISP1 d dp e 10u/16V dig.2 R3 221 R2 102 9012...
Page 289
8.3 Outdoor main PCB REST 10uf/16v VOLTAGE SAMPLE AC-IN 4007 R3 5.1K CURRENT SAMPLE 7042 0057W 4007 +12V +12V +12V 47UF/16v 9013 47uf +12V CURRENT T EST ALRAM ADMC328 5.1K 9013 9013 9013 POS0 POS1 PIO6/CLKOUT PIO7 POS2 PIO5/RFS1 PIO8/AUX0 IC3 74HC04 220uf/25v PIO4...
9 Wiring diagram 9.1 MSH-09HRDN1 indoor unit INDOOR FAN MOTO R LOUVER MOTOR Y /G ROOM TEMP. SENSOR CN13 POWER SUPPLY CN14 CN11 INDOOR PCB CN10 P IPE T EMP. SENS OR YELLO W CN12 DISPLAY BOARD AUTO RESTART (CHOICE) MICRO SWITCH L N S PLASMA...
Page 291
9.3 MSH-12HRDN1 indoor unit INDOOR FAN MOTOR LOUVER MOTOR BLUE BROWN CN13 R OOM TEMP. SENSOR POWER S UPPLY CN14 WHIT E BLACK CN11 INDOOR PCB R E D CN10 CN 4 P IPE TEMP. SENSOR YELLOW CN12 CN 7 DISPLAY BOARD Y/ G AUTO RESTART...
Page 292
10 Electronic function 10.1 Electric Control working environment. 10.1.1 Input voltage: 175~253V. 10.1.2 Input power frequency:50Hz. 10.1.3 Indoor fan normal working amp is less than 1A. 10.1.4 Outdoor fan. Normal working amp is less than 1.5A. 10.1.5 Four-way valve normal working amp is less than 1A. 10.1.6 Swing motor: DC12V.
Page 293
10.3 Protection 10.3.1. 3 minutes delay at restart for compressor. 10.3.2. Temperature protection of compressor top, compressor stops when the temp. of top of compressor is more than 115¡ æ , compressor runs when the temp. of top of compressor is less than 100¡ æ 10.3.3.
Page 294
10.5.5 Current protection Model Current Compressor Current up MSH-12HRDN1 I>12 A Decrease frequency of compressor 10.5A<I<12A I< 10.5A Current down MSH-09HRDN1 I>11.5 A Decrease frequency of compressor 8.5A<I<11.5A I< 8.5A 11.5.6 Rated capacity test Set mode to cooling mode Set temp. to 17°C Set fan speed to high speed Push turbo button 5 times in 10 seconds.
Page 295
function prevails. Anti-cold wind control function at heating mode Condition Indoor fan speed T= Indoor exchanger temp. 34¡ æ Indoor exchanger temp. up T< 34¡ æ 37¡ æ Breeze <T< 37¡ æ 44¡ æ Low speed <T< 44¡ æ Setting fan speed T>...
Page 296
10.8. Defrosting operation (Available for heating only). 10.8.1 Defrosting condition: 10.8.1.1 When outdoor temp. is more than 0¡ æ , Defrosting starts when meeting one of the following conditions, a. The temperature of outdoor heat exchanger remains consecutively lower than 3°c for more than 40 minutes, and the temperature remains consecutively -6°c for more than 3 minutes, b.
Page 297
10.8.4 Rated capacity test Set mode to cooling mode Set temp. to 30 °C Set fan speed to high speed Push turbo button 5 times in 10 seconds. Using special remoter controller After 5 hours, cancel rated capacity test 10.9 Outdoor low temperature protection (optional) Factory standard unit has not this function.
Page 298
constant and the air circulation is kept at low speed (Cold air proof function takes precedence over all). 10.13.4 Auto: The Sleep Mode running function operates in accordance with selected running mode by auto mode. 10.13.5 After 7 hours, unit cancels this modes automatically. 10.14 Auto restart function In case of a sudden power failure, this function automatically sets the unit to previous settings before the power failure when power returns.
Page 299
11.Troubleshooting 11.1 Indoor Unit Error Display Display LED STATUS EEPROM error Indoor / outdoor units communication protection Zero-crossing examination error Fan speed beyond control Open or short circuit of outdoor temperature sensor Room temperature or evaporator temperature sensor open or short circuit of Module protection Over load or too low voltage protection Compressor top protection against temperature...
Page 300
11.1.2 Display LED STATUS Indoor / outdoor units communication protection Is the LED in outdoor main PCB light? check the signal wire between, is it connected good. replace the PCB of indoor unit ,is the unit ok? replace the PCB of power supply board ,is the unit ok? Is the +5 voltage in outdoor main board? Outdoor main...
Page 301
11.1.3 Display LED STATUS Zero-crossing examination error Is power supply right? Is connector connection good? Indoor PCB is defective 11.1.4 Display LED STATUS Fan speed beyond control Is connector connection good? Is voltage being applied to the fan motor? (rang 90v-160v between mid pin and N on CN2 Repair the connector Indoor PCB is defective Indoor fan motor is defective...
Page 302
11.1.6 Display LED STATUS Room temperature or evaporator temperature sensor open or short circuit of Is connection to connector good? Repair connector Replace the sensor 11.1.7 Display LED STATUS Module protection Is connection to connector good? Is the wires to compressor right Repair connector Check the outdoor inverter module.
Page 303
11.1.8 Display LED STATUS Over load or too low voltage protection Is the power supply right? Check the outdoor power board Replace the outdoor power board 11.1.9 Display LED STATUS Compressor top protection against temperature Off: 120c; On: 105c Does compressor operate? Is protector normal? Is refrigerant circulation volume normal? Replace protector...
Page 304
11.1.10 Display LED STATUS Outdoor low temp. protection This is optional, factory standard unit has not this function. Unit stops when outdoor temp. is low than -15°C and lasting time more than 60 minutes, and unit runs again when outdoor temp. more than -12°C. Is the outdoor temp.
Page 310
Max. difference in level Plug type Oper ation temp 17-30 17-30 17-30 17-30 17-30 17-30 Application area 12-16 12-16 14-21 14-21 18-26 18-26 Qty’per 20’ /40’ /40'HQ 130/270/295 130/270/295 130/270/295 130/270/295 113/238/274 113/238/274 1 The noise date is base on hemi-anechoic chamber, during actual operation, these values are normally somewhat different as a result of ambient condition.
Page 311
3.Dimensions 3.1 Indoor unit MSF1-08CR, MSF1-08H R, MSF1-09CR, MSF1-09HR, MSF1-12CR, MSF1-12HR 3.2 Outdoor unit MSF1-08CR, MSF1-08HR, MSF1-09CR, MSF1-09HR Outdoor unit MSF1-12CR, MSF1-12HR...
Page 314
5. Operation limits 5.1 Cooling mode Indoor temperature: 21 Outdoor temperature: 15 5.2 Heating mode Indo or temperature: 20 door temperature: -7 5.3 Dry mode Indo or temperature: 10 Outd oor temperature: 15...
Page 315
6.Wiring diagram 6.1 Cooling only Y/ G INDOOR MOTOR BRO W N/ RED STEP M OTOR PO W ER BLUE CN 5 Y/ G PI PE TEM PERATURE SENSOR BLACK BLACK COMPRESSOR RELAY RO OM TEMPERATURE SENSOR CN 6 DISPLAY BOARD CN12 TRANSFORMER ONLY USED FOR STEEL PACKED M OTOR!
Page 317
7.2 Heating/cooling Y/ G INDOOR MOTOR BR OW N / RED STEP MOTOR POW ER BLUE C N5 C N7 CN 4 Y/ G C N10 PI PE TEMPERATURE SENSOR BLACK BLACK COM PRESSO R RELAY RO OM TEM PERATURE SENSO R C N6 C N9 DI SPLAY BOARD...
Page 319
7. Trouble shooting Failure phenomenon Operation lamp Timer lamp Failure phenomenon oor f an speed has been out of con trol for over 1 minute Indoor room temp. or evaporator sensor is open circuit or short circuit Over current protection of the compressor oc urs 4 times EEROM error r Ex tinguish...
Page 320
7.4 Operation lamp off and Timer lamp flashes Operation lamp off and Timer lamp flashes After changing the main co ntrol bo ard, check if the failure releases The voltage of power supply is too low (less than 187V)? Indoor PCB is defective Power su pply f ault...
Page 321
8 Electronic function 13.2 lectric Control working e nvironme t 8.1.1 nput voltage: 17 Inpu t power f requency:50Hz 8.1.3 Ambient temperature: -7°C~+43°C Indo or fan no rmal w orki ng amp is less than 1A, 8.1.5 Outdoor fan. Normal working amp is less than 1.5A r-way va lve normal working amp is less than 1A.
Page 322
Protection 8.4.7 3 minutes delay at restart for compressor. .4.8 Sensor protection at open circuit and breaking disconnection 8.4.9 Fan Speed is out of c ontrol. When Indoor Fan Speed is too high(higher than High Fan+300RPM)or too lo w(lower than 400RPM), the unit stops and LED displays failure information and can’t returns to normal operation automatically.
Page 323
T> TE6 Evaporator Temp. up T< TE6 >5 Minutes T> TE5 Evaporator Temp. down T< TE5 >5 Minutes 8.10 Dehumidifying mode 8.7.6 The 4-way valve is off in dehumidifying mode 8.7.7 Compressor and Indoor Fan actions in dehumidifying mode Indoor Fan Compressor and Outdoor Fan ON 5minutes Repeat on and off cycle.
Page 324
8.11 Heating mode 8.8.6 Generally, the 4-way valve is open in heating mode, but it is closed in defrosting mode. 8.8.7 Generally, the outdoor fan is turned off with the on-off action of compressor in heating mode, except for the defrosting mode or the end of defrost. 8.8.8 Action of compressor and outdoor fan motor at heating mode: Condition...
Page 325
Defrosting operation (Available for heating only). 8.9.5 Defrosting condition: Defrosting starts when either of the following & : A and B are satisfied: A: The compressor keeps running for 40 minutes or more. B: The temperature difference of evaporator and room temperature meets one of the following: Temp.
Page 326
8.9.8 Defrosting Actions: Defrost for 10 or 6 minutes 25 seconds Compressor 4-way Valve 23 seconds Outdoor Fan 8.10 Automatic operation mode 8.10.5 The air conditioner automatically selects one of the following operation modes: cooling, heating or fan only according to the temp. difference between room temp. (TA) and set temp.
Page 327
8.14.7 Heating: The set temperature decrease 1 per hour. Two hours later, the set temperature will maintain as a constant and the air circulation is kept at low speed (Cold air proof function takes precedence over all). 8.14.8 Auto: The economic running function operates in accordance with selected running mode by auto mode.
Page 339
WINTER OUTDOOR CONDITIONS Indoor 12ºC D 7ºC D 4ºC D 0ºC D -4ºC D -7ºC D 11ºC W 6ºC W 3ºC W -1ºC W -6ºC W -8ºC W Conditions Capacity kW 2.75 2.45 2.17 1.40 1.17 1.13 15ºC Input kW. 0.97 0.86 0.77...
Page 342
WINTER OUTDOOR CONDITIONS 12ºC D 7ºC D 4ºC D 0ºC D -4ºC D -7ºC D Indoor Conditions 11ºC W 6ºC W 3ºC W -1ºC W -6ºC W -8ºC W Capacity kW 4.81 4.28 3.78 2.45 2.04 1.97 15ºC Input kW. 1.61 1.44 1.29...
Page 348
7.1 Electric Control working environment 7.1.1 input voltage: 175~253V 7.1.2 Input power frequency:50Hz 7.1.3 Ambient temperature: -7°C~+45°C 7.1.4 Indoor fan normal working amp is less than 1A, 7.1.5 Outdoor fan. Normal working amp is less than 1.5A 7.1.6 Four-way valve normal working amp is less than 1A. 7.1.7 Swing motor: DC12V.
Page 349
Protection 7.4.1 3 minutes delay at restart for compressor. 7.4.2 Sensor protection at open circuit and breaking disconnection 7.4.3 Fan Speed is out of control. When Indoor Fan Speed is too high(higher than High Fan+300RPM)or too low(lower than 400RPM), the unit stops and LED displays failure information and can’t returns to normal operation automatically.
Page 350
Anti-freezing control to indoor evaporator at cooling mode( T: evaporator temp. ) Condition Compressor Outdoor fan Temp. Time Evaporator T> TE6 Temp. up T< TE6 >5 Minutes Evaporator T> TE5 Temp. down T< TE5 >5 Minutes 7.7 Dehumidifying mode 7.7.1 The 4-way valve is off in dehumidifying mode 7.7.2 Compressor and Indoor Fan actions in dehumidifying mode...
Page 351
T= Indoor exchanger temp. Indoor exchanger temp. up T<TE1 TE1<T<TE2 Breeze T>TE2 Setting fan speed Indoor exchanger temp. down T> TE3 Setting fan speed TE3<T<TE4 Breeze T<TE4 7.8.5 Auto wind at heating mode Condition Indoor fan speed T=Indoor Temp.-Setting Temp. Room temp.
Page 352
If the temp. difference condition is satisfied out of 40 minutes, generally the defrosting time is 6 minutes, after three continuous 6-minute defrost, the fourth should be 10 minutes defrost. The circulation is as following: →7.5-minute defrost → 7.5-minute defrost→7.5-minute defrost→10-minute defrost→ 7.10 Ending condition of defrosting If one of following conditions is satisfied, end the defrost and turn into heating mode:...
Page 353
7.13.3 All protections of remote control cooling are available at forced cooling operation. 7.14 Forced Auto function Select forced auto function with the forced auto button or the switch. In forced auto status the A/C operates at remote control mode with a set temp. of 24 . 7.15 Timer Function 7.16 Economic Running 7.16.1...
8.Troubleshooting 8.1 Display board Infrared Signal Receiver 1: AUTO indicator 2: TIMER indicator 3: PRE.-DEF. Indicator 4: OPERATION indicator 5: SLEEP indicator 8.2 For all heat pump model Failure phenomenon Operation lamp Timer lamp Indoor fan speed has been out of control for over 1 minute Indoor room temp.
Page 357
8.3 Diagnostic Chart 8.3.1 After energizing, no indicator is lighted and the air conditioner can’t be operated. After energizing, the air conditioner can’t be operated Check if AC220V power supply outputs to Indoor PCB. Check if AC220V exists at the primary coil of transformer. Indoor PCB is defective Check if AC14.5V exists at the secondary coil of transformer.
Page 358
8.3.3 Failure phenomenon Failure phenomenon Operation lamp Timer lamp Indoor fan speed has been out of control for over 1 minute Indoor room temp. or evaporator sensor is open circuit or short circuit Over current protection of the compressor occurs 4 times EEROM error No over-zero signal r Extinguish...