Trane Tracer ZN510 Installation, Operation, And Programming page 32

Table of Contents

Advertisement

Table 18: Binary Inputs
Description
Terminals
Binary Input 1
J2-1
J2-2
Binary Input 2
J2-3
J2-4
Binary Input 3
J2-5
J2-6
Table 19: Binary Outputs
Description
Terminals
Binary Output 1
J1-1
Binary Output 2
J1-2
Binary Output 3
J1-4
Binary Output 4
J1-5
Binary Output 5
J1-6
Binary Output 6
J1-7
Table 20: Analog Inputs
Description
Terminals
Zone
TB3-1
Ground
TB3-2
Set
TB3-3
Fan
TB3-4
Ground
TB3-6
Analog Input 1
J3-1
J3-2
Analog Input 2
J3-3
J3-4
Hardware
Specifications
Function
24
VAC
Input
24
VAC
Input
24
VAC
Input
Output
Load Energized
Rating
12 VA
1 VAC RMS (typical)
12 VA
1 VAC RMS (typical)
NOT USED
12 VA
1 VAC RMS (typical)
12 VA
1 VAC RMS (typical)
12 VA
1 VAC RMS (typical)
Function
Zone temperature input
Analog ground
Setpoint input
Fan switch input
Analog ground
Leaving water
temperature
Analog ground
Discharge air temperature -40 to 212 F (-40 to 100 C)
Analog ground
32
Load De-energized
24 VAC RMS (typical)
24 VAC RMS (typical)
24 VAC RMS (typical)
24 VAC RMS (typical)
24 VAC RMS (typical)
Range
5 to 122 F (-15 to 50 C)
NA
40 to 115 F (4.4 to 46.1 C)
= 4821 to 4919 Ohms
OFF
= 2297 to 2342 Ohms
AUTO
NA
-40 to 212 F (-40 to 100 C)
NA
NA