Optional PFCCs
Power factor correction
capacitors (PFCCs) are designed
to provide power factor
correction for the compressor
motor. They are available as an
option.
Note: Remember that the PFCC
nameplate voltage rating must
be greater than or equal to the
compressor voltage rating
stamped on the unit nameplate.
See Table 15 to determine what
PFCC is appropriate for each
compressor voltage application.
CAUTION
Motor of safety overload
damage!
PFCC must be wired into the
starter correctly. Failure to do so
may cause misapplication of
these capacitors and result in a
loss of motor overload
protection and subsequently
cause motor damage.
58
Installation:
Electrical
Table 15. PFCC design voltage sizing per compressor voltage
application
PFCC Design Voltage
480V/60 Hz
600V/60 Hz
2400V/60 Hz
PFCC Rating
480V/50 Hz
4160V/60 Hz
4160V/50 Hz
Figure 15. PFCC leads routed through overload current transformer
Line
PFCC
Overload
Current
Transformer
Load
Motor
Note: See the attached wiring diagram for more detail.
Compressor Motor Rating
(See Unit Nameplate)
380V/60 Hz
440V/60 Hz
460V/60 Hz
480V/60 Hz
575V/60 Hz
600V/60 Hz
2300V/60 Hz
2400V/60 Hz
Compressor Motor Rating
(See Unit Nameplate)
346V/50 HZ
380V/50 HZ
400V/50 Hz
415V/50 Hz
3300V/60 Hz
4160V/60 Hz
6600V/60 Hz
3300V/50 Hz
6600V/50 Hz
Line
Overload
Current
- OR -
Transformer
Motor
PFCC
Load
CVGF-SVN02B-E4