Download Print this page

Trane CVGF-SVN02B-E4 Installation Manual page 41

Gear-driven centrifugal water-cooled liquid chillers, unit model cvgf 400-1000 ton units (50 and 60 hz)

Advertisement

CVGF Rigging
1. Dimensions are in millimeters
(mm). Figure 10.
WARNING
Heavy Objects!
Do not use cables (chains or
slings) except as shown. Each of
the cables (chains or slings)
used to lift the unit must be
capable of supporting the entire
weight of the unit. Lifting cables
(chains or slings) may not be of
the same length. Adjust as
necessary for even unit lift.
Other lifting arrangements may
cause equipment or property-
only damage. Failure to properly
lift unit may result in death or
serious injury. See details below.
1. Use a 3600 mm lifting beam
and adjust the chains (cables)
Figure 10. Rigging diagram with anchor hole
and bolt detail
Control
Panel
See anchor hole
detail
Anchor Bolt Detail
Nuts should not be tight.
Leave 2 to 3 mm gap.
To meet
local codes
Concrete
Recommended procedure to allow for
thermal expansion. (Unless otherwise
specified, parts are furnished by the
customer.)
CVGF-SVN02B-E4
Installation:
Mechanical
for an even, level lift.
2. 900 mm recommended
clearance above highest point of
compressor.
3. Attach safety chains or cables
as shown, and without tension.
The safety chain is not used for
lifting, but is there to prevent
the unit from rolling.
4. More details weight
information is available on
request.
2. Each chain or cable used to lift
the unit must be capable of
supporting the entire weight
of the chiller.
Motor
Terminal Box
Optional unit-
mounted
starter
Unit mounting pad 13 mm
thick (by Trane)
Vibration isolator (by Trane)
75 mm steel pipe
152 × 152 × 19 mm
steel plate
Figure 11. Rigging diagram with safety chain placement
Anchor Hole Detail
4 × 22 mm
diameter holes for
anchoring the unit
Dimensions are typical for each corner
3. Use a 3600 mm lifting beam
and adjust the chains or
cables for an even, level lift.
4. 900 mm recommended
clearance above highest point
of compressor.
5. Attach safety chains or cables
as shown in Figure 11, and
without tension. The safety
chain is not used for lifting,
but is there to prevent the unit
from rolling.
6. More detailed weight
information is available upon
request.
Evaporator
tubesheet
41

Hide quick links:

Advertisement

loading

This manual is also suitable for:

Cvgf400Cvgf1000Cvgf500Cvgf650Cvgf700Cvgf800