Download Print this page

Trane CVGF-SVN02B-E4 Installation Manual page 35

Gear-driven centrifugal water-cooled liquid chillers, unit model cvgf 400-1000 ton units (50 and 60 hz)

Advertisement

CVGF-SVN02B-E4
Installation:
Mechanical
Figure 5. Recommended operating and service clearances –
Model CVGF without unit-mounted starters
CL1/CL2
Table 8. Dimensions for figure 5
Compressor
Shell Size
400-500
500
560-700
700
740-1000
1000
Notes:
CL1 at either end of the machine and is required for tube pull clearance.
CL2 is always at the opposite end of the machine from CL1 and is required for service clearance.
Add 14-5/8" (37.1 cm) on each end for the water box.
36" (914 mm)
Recommended
Width
Length
36" (914 mm)
Recommended
clearance
Unit Dimensions Without Unit
Clearance Tube Pull
Feet-Inch (mm)
Dimensions Feet-Inch (m-meters)
CL1
CL2
Length
13' 11"
3' 7"
13' 5"
(4.235)
(1.092)
(4.083)
13' 11"
3' 7"
13' 5"
(4.235)
(1.092)
(4.083)
13' 11"
3' 7"
13' 5"
(4.235)
(1.092)
(4.083)
clearance
Height
18" (457 mm)
Recommended
clearance
CL1/CL2
Mounted Starters
Height
Width
6' 11"
6' 3"
(1.790)
(1.913)
6' 11"
6' 7"
(1.790)
(2.028)
8' 4"
7' 5"
(2.540)
(2.261)
35

Hide quick links:

Advertisement

loading

This manual is also suitable for:

Cvgf400Cvgf1000Cvgf500Cvgf650Cvgf700Cvgf800