Commissioning, inspection, maintenance
Further details regarding the individual steps
Designating heating circuits – only for weather-compensated
control units
In the delivered condition, the heating
circuits are designated "Heating circuit
1", "Heating circuit 2" and "Heating cir-
cuit 3" (if installed).
If the system user prefers, the heating
circuits can be designated differently to
suit the specific system.

Checking the gas type

The boiler is equipped with an electronic combustion controller that adjusts the burner
for optimum combustion in accordance with the prevailing gas quality.
■ Consequently, for natural gas there is no adjustment required across the entire
Wobbe index range.
The boiler can be operated in the Wobbe index range 9.5 to 15.2 kWh/m
3
54.7 MJ/m
).
■ Convert the burner for operation with LPG (see "Gas type conversion" on
page 13).
1. Determine the gas type and Wobbe
index by asking your local gas supply
utility or LPG supplier.
2. Convert the burner for operation with
LPG (see page 13).
12
(cont.)
Enter names for heating circuits:
Operating instructions
3. Record the gas type in the service
report on page 142.