Viessmann VITODENS 200-W Service Instructions Manual page 101

Wall mounted gas condensing boiler natural gas and lpg version
Table of Contents

Advertisement

Fault codes
(cont.)
Dis-
Const.
Weath.-
played
comp.
fault
code
bd
X
bE
X
bF
X
C1
X
X
C2
X
X
C3
X
X
C4
X
X
C5
X
X
System char-
Cause
acteristics
Control mode
Communica-
without remote
tion error,
control
remote con-
trol Vitotrol
heating circuit
2 (with mixer)
Control mode
Communica-
without remote
tion error,
control
remote con-
trol Vitotrol
heating circuit
3 (with mixer)
Control mode
Incorrect
LON commu-
nication mod-
ule
Control mode
Communica-
tion error
extension
EA1
Control mode
Communica-
tion error,
solar control
module or
Vitosolic
Control mode
Extension
AM1 commu-
nication error
Control mode
Communica-
tion error,
Open Therm
extension
Control mode,
Communica-
max. pump
tion error, var-
speed
iable speed
internal pump
Troubleshooting
Measures
Check connec-
tions, lead, coding
address "A0" and
remote control set-
tings (see
page 132)
Check connec-
tions, lead, coding
address "A0" and
remote control set-
tings (see
page 132)
Replace the LON
communication
module
Check electrical
connections
Check solar control
module or
Vitosolic
Check electrical
connections
Check Open
Therm extension
Check the setting
of coding address
"30"
101