Viessmann VITODENS 200-W Service Instructions Manual page 78

Wall mounted gas condensing boiler natural gas and lpg version
Table of Contents

Advertisement

Code 2
Heating circuit 1, heating circuit 2, heating...
Coding in the delivered condition
A4:0
With frost protection (only
for weather-compensa-
ted control units)
A5:5
With heating circuit pump
logic function (economy
circuit): Heating circuit
pump "OFF" when the
outside temperature (AT)
is 1 K higher than the set
room temperature (RT
AT > RT
weather-compensated
control units)
Parameter address
A5:...
1
2
3
4
5
6
7
to
15
78
Possible change
A4:1
A5:0
A5:1
to
A5:15
)
set
+ 1 K (only for
set
With heating circuit pump logic function: Heating cir-
cuit pump "OFF"
AT > RT
+ 5 K
set
AT > RT
+ 4 K
set
AT > RT
+ 3 K
set
AT > RT
+ 2 K
set
AT > RT
+ 1 K
set
AT > RT
set
AT > RT
- 1 K
set
AT > RT
- 9 K
set
(cont.)
No frost protection; this set-
ting is only possible if code
"A3: -9" has been selec-
ted.
Note
Observe the information
regarding coding address
"A3"
Without heating circuit
pump logic function
With heating circuit pump
logic function: Heating cir-
cuit pump "OFF" (see the
following table)