Viessmann VITODENS 200-W Service Instructions Manual page 103

Wall mounted gas condensing boiler natural gas and lpg version
Table of Contents

Advertisement

Fault codes
(cont.)
Dis-
Const.
Weath.-
played
comp.
fault
code
d6
X
X
d7
X
X
d8
X
X
dA
X
db
X
dC
X
dd
X
dE
X
System char-
Cause
acteristics
Control mode
Input DE1
fault at exten-
sion EA1
Control mode
Input DE2
fault at exten-
sion EA1
Control mode
Input DE3
fault at exten-
sion EA1
Control mode
Short circuit,
without room
room temper-
influence
ature sensor,
heating circuit
1 (without
mixer)
Control mode
Short circuit,
without room
room temper-
influence
ature sensor,
heating circuit
2 (with mixer)
Control mode
Short circuit,
without room
room temper-
influence
ature sensor,
heating circuit
3 (with mixer)
Control mode
Lead break,
without room
room temper-
influence
ature sensor,
heating circuit
1 (without
mixer)
Control mode
Lead break,
without room
room temper-
influence
ature sensor,
heating circuit
2 (with mixer)
Troubleshooting
Measures
Check connection
to input DE1
Check connection
to input DE2
Check connection
to input DE3
Check room tem-
perature sensor,
heating circuit 1
Check room tem-
perature sensor,
heating circuit 2
Check room tem-
perature sensor,
heating circuit 3
Check room tem-
perature sensor for
heating circuit 1
and remote control
settings (see
page 132)
Check room tem-
perature sensor for
heating circuit 2
and remote control
settings (see
page 132)
103