Venting The Boiler By Flushing; Selecting The Language (If Required) - Only For Weather-Compensated Control Units; Setting The Time And Date (If Required) - Only For Weather-Compensated Control Units - Viessmann VITODENS 200-W Service Instructions Manual

Wall mounted gas condensing boiler natural gas and lpg version
Table of Contents

Advertisement

Commissioning, inspection, maintenance
Further details regarding the individual steps

Venting the boiler by flushing

B
Selecting the language (if required) – only for weather-compen-
sated control units
Note
At the commissioning stage, the display
is in German (default setting)
Extended menu:
1. å
2. "Settings"
Setting the time and date (if required) – only for weather-com-
pensated control units
During commissioning, or after pro-
longed time out of use, the time and date
need to be reset.
10
1. Close the shut-off valves on the heat-
ing water side.
2. Connect the drain hose at boiler drain
& fill valve B (on the connection set,
accessories or on-site).
3. Open valves A and B and vent
using mains pressure until no more
air noise is audible.
A
4. Close valves A and B and open
the heating water shut-off valves.
3. "Language"
Sprache
Deutsch
Cesky
Dansk
English
4. Set the required language with / .
Extended menu:
1. å
2. "Settings"
(cont.)
DE
ç
CZ
DK
GB
Wählen mit