Commissioning, inspection, maintenance
Venting the heating system
Activating the venting function
Weather-compensated control unit
Service menu
1. Press OK and
simultaneously for approx. 4 s.
å
2. "Service functions"
3. "Venting"
Venting function is enabled.
4. Ending venting function:
Press OK or
.
ä
Filling the siphon with water
Multi-boiler system:
Fill the siphon in the flue gas header with water as
well.
A
B
Fig. 19
1. Remove retaining clip
2. Fill siphon
with water.
B
Checking all connections on the heating water side and DHW side for leaks
Designating heating circuits - only for weather-compensated control units
In the delivered condition, heating circuits are designa-
ted "Heating circuit 1", "Heating circuit 2" and
"Heating circuit 3" (if installed).
If the system user prefers, heating circuits can be re-
designated to suit the specific system.
24
(cont.)
and siphon
.
A
B
Constant temperature control unit
Service menu
1. Press OK and
simultaneously for approx. 4 s.
å
2. Select "
5
" with
and confirm with OK.
Ú
"ON" flashes.
3. Activate the venting function with OK.
"EL on" is shown constantly.
4. Ending venting function:
Press
.
ä
3. Mount siphon
and secure with retaining clip
B
Note
Never twist the inlet hose during assembly. Route
the drain hose without any bends and with a con-
stant fall.
To enter names for heating circuits:
Operating instructions
.
A