Setting The Maximum Output - Viessmann VITODENS 200-W Service Instructions Manual

Wall mounted gas condensing boiler natural gas and lpg version
Table of Contents

Advertisement

Further details regarding the individual steps
Supply (flow) pres-
Supply (flow)
sure for natural
pressure for LPG
gas
below 15 mbar
below 42.5 mbar
15 to 25 mbar
42.5 to 57.5 mbar
above 25 mbar
above 57.5 mbar

Setting the maximum output

You can limit the maximum output for heating operation. The limit is set via the
modulation range. The max. adjustable heating output is limited upwards by the boiler
coding card.
Weather-compensated control unit:
1. Press OK and å simultaneously
for approx. 4 s.
2. "Service functions"
3. "Max. output"
4. "Change?" Select "Yes".
A value flashes on the display (e.g.
"85"). In the delivered condition, this
value represents 100 % of rated out-
put.
5. Select required value.
Commissioning, inspection, maintenance
(cont.)
Measures
Do not start the boiler. Notify your gas
supply utility or LPG supplier.
Start the boiler.
Install a separate gas pressure governor
upstream of the system and regulate the
pre-charge pressure to 20 mbar for natu-
ral gas or 50 mbar for LPG. Notify your
gas supply utility or LPG supplier.
Constant temperature control unit:
1. Press OK and å simultaneously
for approx. 4 s.
2. Select Ú "3" and confirm with OK.
A value flashes on the display (e.g.
"85") and "A" appears. In the deliv-
ered condition, this value represents
100 % of rated output.
3. Select required value and confirm
with OK.
17