Heating circuit 1, heating circuit 2, heating...
Coding in the delivered condition
E8:1
Minimum speed in opera-
tion with reduced room
temperature subject to
the setting in coding
address "E9" (only for
weather-compensated
control units)
E9:45
Speed of the variable
speed heating circuit
pump: 45 % of the maxi-
mum speed during oper-
ation with reduced room
temperature (only for
weather-compensated
control units)
F1:0
Screed drying function
disabled (only for
weather-compensated
control units)
F2:8
Time limit for party mode
or external heating pro-
gram changeover via key:
8 h (only for weather-
compensated control
*1
units)
F5:12
Run-on time of the circu-
lation pump in the heating
circuit connection set in
heating mode: 12 min
(only for constant temper-
ature control units)
*1
Party mode ends automatically in the "Heating and DHW" program, when the
system changes over to operation with standard room temperature.
(cont.)
Possible change
E8:0
Speed subject to the set-
ting in coding address
"E7"
E9:0
Speed adjustable from 0 to
to
100 % of the maximum
E9:100
speed during operation
with reduced room temper-
ature
F1:1
Screed drying function
to
adjustable in accordance
F1:6
with 6 optional tempera-
ture/time profiles (see
page 127)
F1:15
Constant flow temperature
20 °C
F2:0
No time limit for party
*1
mode
F2:1
Time limit adjustable from 1
to
*1
to 12h
F2:12
F5:0
No run-on time for the cir-
culation pump in the heat-
ing circuit connection set
F5:1
Run-on time of the circula-
to
tion pump in the heating cir-
F5:20
cuit connection set adjust-
able from 1 to 20 min
Code 2
83