Venting The Boiler By Flushing - Viessmann VITODENS 100-W Installation And Service Instructions Manual

Type b1hc, b1kc, 4.7 to 35.0 kw wall mounted gas condensing boiler
Hide thumbs Also See for VITODENS 100-W:
Table of Contents

Advertisement

Filling the heating system
Gas condensing system boiler
B
Fig. 18
Gas condensing combi boiler
B
Fig. 19

Venting the boiler by flushing

Note
Inadequate venting can result in damage due to steam
blasts in the heat exchanger.
(cont.)
C
A
D
C A
Commissioning, inspection, maintenance
1. Open shut-off valves
A
2. Connect fill hose to valve
3. Fill the heating system. Minimum system pressure
0.8 bar (80 kPa).
4. Close valve
.
C
1. Open shut-off valves
A
2. Open valves
and
C
D
Note
The cold water supply must be open.
3. Fill the heating system. Minimum system pressure
0.8 bar (80 kPa).
4. Close valves
and
C
D
5. Remove the connection line between valves
and
. During operation, the connection must be
D
interrupted.
and (if fitted)
.
B
and open valve
.
C
C
and (if fitted)
.
B
.
.
C
23