Advertisement

VIESMANN
Service instructions
for contractors
Vitosol-F
For applicability, see the last page
VITOSOL-F
Please keep safe.
5692 808 GB
3/2009

Advertisement

Table of Contents
loading

Summary of Contents for Viessmann Vitosol-F

  • Page 1 VIESMANN Service instructions for contractors Vitosol-F For applicability, see the last page VITOSOL-F Please keep safe. 5692 808 GB 3/2009...
  • Page 2: Safety Instructions

    Observe the following when working on Replace faulty components only this system with original Viessmann spare ■ all legal instructions regarding the pre- parts. vention of accidents, ■ all legal instructions regarding envi- ronmental protection, ■...
  • Page 3 Installing non-authorised components and non-approved modifications or conversions can compromise safety and may invalidate our warranty. For replacements, use only orig- inal spare parts supplied or approved by Viessmann.
  • Page 4: Table Of Contents

    Index Index Commissioning, inspection, maintenance Steps - commissioning, inspection and maintenance.......... Further details regarding the individual steps............Parts lists Parts list Vitosol 200-F, 300-F................11 Specification Vitosol 200-F......................13 Vitosol 300-F......................13 Solar-Divicon (accessory)..................13 Heat transfer medium (accessory)............... 13 Certificates Declaration of conformity..................
  • Page 5: Commissioning, Inspection, Maintenance

    Commissioning, inspection, maintenance Steps - commissioning, inspection and maintenance For further information regarding the individual steps, see the page indicated Commissioning steps Inspection steps Maintenance steps Page • 1. Flushing, testing for leaks and filling the solar thermal system................• •...
  • Page 6: Further Details Regarding The Individual Steps

    Commissioning, inspection, maintenance Further details regarding the individual steps Flushing, testing for leaks and filling the solar thermal system ■ Never drain the system with a vacuum Notes pump. ■ Check the system for leaks: ■ A heat transfer medium containing gly- The collector in its cold state must be col can deteriorate if it is exposed to subject to a positive pressure of at...
  • Page 7: Checking The Expansion Vessel And The System Pressure

    Commissioning, inspection, maintenance Further details regarding the individual steps (cont.) Checking the expansion vessel and the system pressure 1. Drain the system. For this, close the 3. Top-up heat transfer medium until the cap valve on the expansion vessel (if system pressure is 0.3 to 0.5 bar installed) and reduce the pressure.
  • Page 8: Venting The Solar Thermal System

    Commissioning, inspection, maintenance Further details regarding the individual steps (cont.) Venting the solar thermal system 1. Open the air vent valve. 3. Repeat the venting process after the Vent the circulation pumps. For this, system has been operational for sev- adjust the circulation pumps to their eral days.
  • Page 9: Checking The Switching Function Of The Solar Control Unit

    Commissioning, inspection, maintenance Further details regarding the individual steps (cont.) High-flow operation, 40 l/(h·m Low-flow operation, 15 l/(h·m Number of Flow rate in l/min Number of Flow rate in l/min collectors collectors 10.5 12.5 15.5 18.5 10.5 21.5 11.5 23.5 Checking the switching function of the solar control unit Solar control unit installation and service instructions...
  • Page 10: Checking The Frost Protection Temperature And The Ph Value Of The Heat Transfer Medium

    Check the pH value using the pH strip in of the "Tyfocor LS" heat transfer medium the solar service case (accessory). with a Viessmann antifreeze tester or the manual refractometer in the solar service Solar service case operating case (accessory).
  • Page 11: Parts Lists

    Parts lists Parts list Vitosol 200-F, 300-F When ordering spare parts: 014 Profile clip Quote the part and serial no. (see type 015 Diagonal sealing strip plate) and the position no. of the required 016 Support sleeve part (as per this parts list). 017 Resilient buffer Obtain standard parts from your local 018 Mounting bracket...
  • Page 12 Parts lists Parts list Vitosol 200-F, 300-F (cont.)
  • Page 13: Specification

    Specification Vitosol 200-F Type SV/SH Absorber area 2.31 4.76 Aperture area 2.33 4.96 Thermal capacity c 5.35 6.40 kJ/(m ·K) Max. idle temperature °C Permiss. operating pressure Content, heat transfer medium litres 1.83/2.48 Vitosol 300-F Type SV/SH Absorber area 2.32 Aperture area 2.33 Thermal capacity c...
  • Page 14 Specification Heat transfer medium (accessory) (cont.) TYFOROP CHEMIE GmbH Anton-Rée-Weg 7 D - 20537 Hamburg e-mail: info@tyfo.de Internet: www.tyfo.de...
  • Page 15: Certificates

    Certificates Declaration of conformity We, Viessmann Werke GmbH & Co KG, D-35107 Allendorf, declare as sole respon- sible body, that the products Vitosol 200-F and 300-F conform to the following standards: DIN 1055 EN 12975 to solar KEYMARK In accordance with the following directives, these products are designated _:...
  • Page 16 Vitosol 300-F, type SH3A part no. 7374 163 Vitosol 300-F, type SV3B part no. 7417 765 Vitosol 300-F, type SH3B part no. 7417 766 Viessmann Werke GmbH&Co KG Viessmann Limited D-35107 Allendorf Hortonwood 30, Telford Telephone: +49 6452 70-0 Shropshire, TF1 7YP, GB...

Table of Contents