These venting systems, in combination with the L900, have been tested and listed as a direct vent system by Warnock Hersey. The location of the
termination cap must conform to the requirements in the Vent Terminal Locations diagram from the "Exterior Vent Termination Locations" section.
FPI Direct Vent (Flex) System Termination Kits include all the
parts needed to install the L900 using a fl exible vent.
FPI Kit #
Length
Contains:
#946-618
6 Feet
1)
8" fl exible liner (Kit length)
2)
5" fl exible liner (Kit length)
3)
spring spacers (3)
4)
thimble (2)
5)
AstroCap termination cap (1)
6)
screws (12)
#946-616
10 Feet
7)
tube of Mill Pac (1)
8)
plated screws (8)
9)
S.S. screws #8 x 1-1/2" drill point, (4)
10) vinyl siding standoff
5" dia. flue pipe
8" dia.
Flue pipe
Regency
®
L900 Direct Vent Gas Fireplace
VENTING ARRANGEMENTS
HORIZONTAL TERMINATION (FLEX)
Regency
®
Direct Vent System
Vinyl Siding
Standoff
Wall Thimble
(Mandatory in all
Horizontal Terminations)
spring spacer
INSTALLATION
Vent Guard - if required*
TM
AstroCap XL
Termination Cap
(Part #946-623/P)
* A Vent Guard is required when the AstroCap
is installed above grade at 7 feet or lower.
Notes:
1) Liner sections should be continuous without any joints
or seams.
2) Only Flex pipe purchased from FPI may be used for Flex
installations.
3) Horizontal vent must be supported every 3 feet.
4) A wall thimble is mandatory for all horizontal terminations
due to high temperatures.
(Part #946-506/P)
15