7. Ensure that the metallic underside of the wrist strap is in direct contact with your
skin.
The wrist strap should be snug around the wrist so that it does not rotate. (See
"Antistatic Precautions" on page
Caution – Before handling FRUs, be sure to connect the clip of the antistatic wrist strap
and of the antistatic mat to the server grounding port, and attach the band of the wrist strap
to one of your wrists. Place the FRUs on the grounded antistatic mat. Failure to take these
antistatic measures might result in serious damage.
8. Place the additional rack-mountable dual power feed on an antistatic mat.
9. Mount the rack-mountable dual power feed.
a. Remove the six dummy panels from the bottom of the equipment rack of the
M8000 server.
b. Remove the cover panel (together with four screws) of the M8000 server, and
mount the two bus bars (L shape) from the installation kit by using two bolts.
[Torque: 8.24 N•m (84 kgf•cm)]
c. Remove the connector panel (together with a thumb screw) of the M8000 server,
and mount it (with a thumb screw) on the mounting bracket from the installation
kit.
d. Mount the mounting bracket on the M8000 server (with four screws, at the
mounting location of the covering panel).
e. Mount the cage nuts from the installation kit on the two poles (two for each pole)
at the rear of the equipment rack of the M8000 server.
Chapter 24
Addition and Deletion of a RDPF Option, Power Cabinet, and M9000 Expansion Cabinet
1-9)
Section 1.4,
24-5