Electronic Control: Testing, Error Codes, Rebooting; Automatic Component Protection - Friedrich WallMaster WS08C10 Service Manual

Thru-the-wall air conditioners and heat pumps
Hide thumbs Also See for WallMaster WS08C10:
Table of Contents

Advertisement

ELECTRONIC CONTROL PANEL
PM
Fan
Speed
Mode
Timer
Set
Hour
On/Off
Figure 4: "WS" Cooling only models
Electronic Control Panel
TESTING THE ELECTRONIC CONTROL
ACTIVATING TEST MODE
Activate Test Mode by pressing at the same time, the Mode
button and the Temp/Hour
The LEDs for Set/Hour: "Start Time" and "Stop Time" will
blink 1 bps while Test Mode is active.
Test Mode has a duration of 90 minutes. Test Mode can be
activated under any function, including Off.
Test Mode is cancelled by pressing the Power (on/off)
button, unplugging the unit, or when the 90 minutes times
out.
Test Mode settings are factory default of:
Unit operation On, MoneySaver On, Cool Mode, 60
degrees F, speed fan on High. "Timer" and "Set Hour"
features are non-functional.
Test Mode overrides the three minute compressor Lock-
out, all delays for fan motor start, speed change, and when
switching modes.
ERROR CODE MODE
Error Code Mode is used to display all error codes
stored since reset. It is a sub-mode of Test Mode. Unit
must be in Test Mode to enter the Error Code function.
Activating Error Code Mode: Press the TIMER On/Off"
button (see fi gures 4 and 5). The LED for the TIMER On/
Off will fl ash 1 bps (beats per second) while Error Code
Mode is active. Pressing the Temp/Hour
display "00". Consecutive presses will scroll through all
error codes stored. Press the Temp/Hour
see the reverse order of the error codes. When the end
of the stored error codes is reached the temperature Set
Point will appear. (Each error code is listed once)
Power
Cool
®
Money Saver
Fan Only
Clock
Start Time
Stop Time
Temp/Hour
button (see fi gures 4 and 5).
button will
button to
PM
2
3
4
8
Fan
Smart
9
Mode
Speed
Fan
Money
Timer
Set
14
Saver
On/Off
Hour
13
10 11 12
Figure 5: "WE"/"WY" heat/cool models
Electronic Control Panel
Exiting Error Code Mode: press the Timer On/Off
button.
Clearing Error Codes: Error codes are cleared
from the memory by exiting from Error Code Mode.
MEMORY
The electronic control has a memory to retain all
functions and settings, as set up by the user, in the event
of a power failure. For example: once power is restored
to the unit, there is a two second delay before the fan
comes on and approximately three minutes delay before
the compressor is activated providing that the mode was
set for cooling and the set point temperature has not
been met in the room.

Automatic component protection

Your unit is equipped with Automatic Component Protection.
To protect the compressor of the unit, there is a three minute delay
if you turn the unit off or if power is interrupted. The fan will not be
affected. Also, if you switch from Cool mode to Fan Only mode, and
switch back to Cool mode, there is a three-minute delay before the
compressor comes back on.