Server Specific Map Descriptor Parameters - Data Table Read/Write; Driver Related Map Descriptor Parameters - Pccc - FieldServer FS-8704-14 Driver Manual

Ethernet/ip
Hide thumbs Also See for FS-8704-14:
Table of Contents

Advertisement

FS-8704-14 EtherNet/IP Manual
6.3.3 Server Specific Map Descriptor Parameters – Data Table Read/Write.
Column Title
EIP_Service
EIP_Tag_Name
EIP_Data_Type*
Length
EIP_Structure_Handle*
6.3.4 Driver Related Map Descriptor Parameter s – PCCC
Column Title
Function
EIP_Con_Typ
The type of data transfer required
EIP_Service
Action to be performed
File_Type
Allen Bradley file type
File_Number
Allen Bradley file number
Number of data elements to be mapped. If the number of data
elements exceeds the Map Descriptor length, the list of data
Length
elements will be truncated and an error message will be printed
once per Map Descriptor.
information.
Address
Address in the file
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com
Tel: (408) 262 2299 Fax: (408) 262 2269 Toll Free: (888) 509 1970 email: support@fieldserver.com
Function
The action to be performed.
Tag name expressed in PLC program. The data type of this
parameter is used to set the data format of the Data Array
if the EIP_Data_Type parameter is not specified.
If set, the data will be stored in the specified format which
may be different to the format of the tag being polled. If
the parameter is not set, the data type of the Data Array
will be used. This is only applicable to Data Table Read
when FieldServer is the Server. Refer to Appendix A.4 for
further information.
Number of data elements to be mapped. If the number of
data elements exceeds the Map Descriptor length, the list
of data elements will be truncated and an error message
will be printed once per Map Descriptor.
Appendix D for further information.
This parameter is required only for read structures i.e.
where EIP_Service is Data_Table_Read.
supports read structures having members of same type,
i.e. all members are of type Byte, Uint16, Uint32 or Float
etc.
When this parameter is defined, the number of
structure members must be specified as the length of the
Map Descriptor.
Refer to Appendix D for further
Page 14 of 30
Legal Values
Data_Table_Read,
Data_Table_Write
Maximum
characters.
Float, Uint16, Uint32, Bit,
Byte, Boolean, -
For
any
Descriptor there can be
200 Floats, 400 Integers
Refer to
or 800 Bytes
The driver
Any 16bit Integer number
e.g. 59592, 0
Legal Values
Explicit
EXEC_PCCC
(Encapsulation
using Allen Bradley PCCC)
N Integer
F Float
O Output
B Boolean
I Input
S Status
Any valid numerical value
For
any
given
Descriptor there can be 61
Floats, 122 Integers or 244
Bytes. .
Any valid numerical value
between 0 to 255
length
48
given
Map
Map