FS-8700-127 Hanning & Kahl HCS-R Manual
4

DATA ARRAY PARAMETERS

Data Arrays are "protocol neutral" data buffers for storage of data to be passed between protocols. It is necessary
to declare the data format of each of the Data Arrays to facilitate correct storage of the relevant data.
Section Title
Data_Arrays
Column Title
Function
Data_Array_Name
Provide name for Data Array
Provide data format. Each Data Array can only take on one
Data_Array_Format
format.
Number of Data Objects. Must be larger than the data storage
Data_Array_Length
area required by the Map Descriptors for the data being placed in
this array.
Example
// Data Arrays
Data_Arrays
Data_Array_Name
, Data_Array_Format
DA_CURRENT
, Uint16
DI_FromLoop01
, Bit
DI_OnLoop01
, Bit
DI_FromLoop02
, Bit
DI_OnLoop02
, Bit
DI_FromLoop03
, Bit
DI_OnLoop03
, Bit
DI_FromLoop014
, Bit
DI_OnLoop04
, Bit
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.FieldServer.com
Tel: 408 262-2299 Fax: 408-262-2269 Toll_Free: 888-509-1970 email: support@FieldServer.com
, Data_Array_Length
, 22
, 22
, 22
, 22
, 22
, 22
, 22
, 22
, 22
Page 5 of 17
Legal Values
Up
to
15
alphanumeric
characters
Float,
Bit,
UInt16,
SInt16, Byte.
1-10, 000