Appendix A.7.7. Map Descriptor Example - Set Up A Permanent Static Recipient List - FieldServer FS-8700-73 Driver Manual

Bacnet mstp - serial
Hide thumbs Also See for FS-8700-73:
Table of Contents

Advertisement

FS-8700-73 BACnet MSTP Driver Manual
A BACnet EventNotification message contains a Priority field indicating the priority of the event being reported. The Priority values to be used are configured via the
Priority property of the Notification Class object, using the configuration file parameters Pri_to_offnormal, Pri_to_normal and Pri_to_fault, which determine the priorities
to be used respectively for all to-offnormal, to-normal and to-fault transitions reported via the Notification Class object.
Priority Values should be chosen as follows:
Alarm and Event Priority
Network Priority
00-63
Life Safety Message
64-127
Critical Equipment Message
128-191
Urgent Message
192-255
Normal Message
Appendix A.7.7.
Map Descriptor Example – Set up a Permanent Static Recipient List
A permanent static RecipientList may be configured directly on the FieldServer, eliminating the need for a remote workstation to modify the RecipientList in order to
receive Event Notifications. Using this option makes the RecipientList read-only, i.e. it can then only be modified via the FieldServer config.csv file.
This is done by adding an Event_Receiver section to the config.csv. This section must appear after the definition and all other references to the relevant Notification Class
object.
Map_Descriptors
Map_Descriptor_Name
, Data_Array_Name
, Data_Array_Offset
BAC_NC_P1
, DA_NC_01
, 0
Notification Class Objects are configured as Map Descriptors. Each Notification Class Object maintains a RecipientList Property which may contain multiple destinations.
Each destination is configured as an Event_Receiver after the relevant Notification Class Object has been configured.
Map_Descriptors
Map_Descriptor_Name
, Data_Array_Name
, Data_Array_Offset
CMD_AI_01
, DA_AI_01
, 10
Event_Receiver
Node_Name
, Node_ID
, Protocol
, Process_ID
OWS_01
, 10
, BACnet_MSTP
, 12345
OWS_02
, 12
, BACnet_MSTP
, 56789
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.FieldServer.com
Tel: (408) 262-2299 Fax: (408) 262-2269 Toll Free: (888) 509-1970 email: support@FieldServer.com
, Function
, Node_Name
, Object_Type
, Passive
, Virtual_DEV_11
, NC
, Function
, Node_Name
, Object_Type
, Passive
, Virtual_DEV_11
, AI
This section sets up RecipientList entries for the defined Notification Class map
, Notification_Class_MD
, Adapter
descriptor. It must appear at the end of the configuration, after all other
, BAC_NC_P1
, N1
, BAC_NC_P1
, N1
references to the Notification Class map descriptor.
Page 27 of 48
, Object_Instance
, Ack_Required
, 1
, No
, Object_Instance
, Notification_Class
, Low_Alarm
, 1
, BAC_NC_P1
, 20
This is the Notification Class
map descriptor governing the
sending of Event Notifications
(Intrinsic Alarming)
This is a BACnet Object that
, High_Alarm
will report its alarms via the
, 30
Notification
Class
descriptor BAC_NC_P1
map